Omron CS1G/H-CPUxxH Instructions Manual page 344

Sysmac cs series; sysmac cj series
Hide thumbs Also See for CS1G/H-CPUxxH:
Table of Contents

Advertisement

Data Shift Instructions
Operand Specifications
Description
Flags
Precautions
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Counter Area
DM Area
EM Area without bank
EM Area with bank
Indirect DM/EM
addresses in binary
Indirect DM/EM
addresses in BCD
Constants
Data Registers
Index Registers
Indirect addressing
using Index Registers
ASRL(571) shifts the contents of Wd and Wd +1 one bit to the right (from left-
most bit to rightmost bit). "0" will be placed in the leftmost bit of Wd +1 and the
contents of the rightmost bit of Wd will be shifted into the Carry Flag (CY).
Wd+1
Name
Label
Error Flag
ER
Equals Flag
=
Carry Flag
CY
Negative Flag
N
When ASRL (571) is executed, the Error Flag and the Negative Flag will turn
OFF.
If as a result of the shift the contents of Wd and Wd +1 are zero, the Equals
Flag will turn ON.
CIO 0000 to CIO 6142
W000 to W510
H000 to H510
A448 to A958
T0000 to T4094
C0000 to C4094
D00000 to D32766
E00000 to E32766
En_00000 to En_32766
(n = 0 to C)
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
---
---
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Wd
Operation
OFF
ON when the shift result is 0.
OFF in all other cases.
ON when 1 is shifted into the Carry Flag (CY).
OFF in all other cases.
OFF
Section 3-9
Wd
323