Timer and Counter Instructions
3-6-6
MULTI-OUTPUT TIMER: MTIM(543)/MTIMX(554)
Purpose
Ladder Symbol
Variations
Applicable Program Areas
Operands
226
MTIM(543)/MTIMX(554) operates a 0.1-s incrementing timer with eight inde-
pendent SVs and Completion Flags. The set value is 0 to 999.9 s for
MTIM(543) and 0 to 6,553.5 s for MTIMX(554), and the timer accuracy is 0 to
0.01 s.
Note The timer accuracy for CS1D CPU Units is 10 ms + the cycle time
BCD
Binary
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program areas
Not allowed
D1: Completion Flags
D1 contains the eight Completion Flags as well as the pause and reset bits.
D1
D2: PV Word
D2 contains the 4-digit binary or BCD PV.
Data
BCD
Binary
MTIM(543)
D1
D1: Completion Flags
D2
D2: PV word
S
S: First SV word
MTIMX(554)
D1
D1: Completion Flags
D2
D2: PV word
S
S: First SV word
Step program areas
OK
15
9 8
7
6
5
Do not use.
Reset bit
Pause bit
Range
#0000 to #9999
&0 to &65535 (decimal)
#0000 to #FFFF (hex)
Section 3-6
MTIM(543)/
MTIMX(554)
Not supported.
Not supported.
Subroutines
Interrupt tasks
OK
Not allowed
4
3
2
1
0
Completion Flags