Failure Diagnosis Instructions
946
Note Unlike user-defined fatal errors, system errors generated by FALS(007) will
clear I/O memory if the IOM Hold Bit is OFF. The following areas will be
cleared: CIO Area, Work Area, Timer Flags and PVs, Index Registers, and
Data registers.
The following table shows how to specify error codes and error details in S
and S+1.
Error name
Error code
Memory Error
80F1 Hex
I/O Bus Error
80C0 Hex
Unit Number
80E9 Hex
Duplication
Error
Rack Number
80EA Hex
Duplication
Error
Fatal Inner
82F0 Hex
Board Error
S
• Bits 00 to 09: Memory Error Location
Bit 00: User program
Bit 04: PLC Setup
Bit 05: Registered I/O table
Bit 07: Routing table
Bit 08: CPU Bus Unit Setup
Bit 09: Memory Card transfer error
• Bits 10 to 15: Invalid
• Bits 00 to 07: Slot number where the I/O Bus error
occurred
Slot 0 to 9: 00 to 09 Hex
Slot unknown: 0F Hex
• Bits 08 to 15: Rack number where the I/O Bus
error occurred
Slot 0 to 7: 00 to 07 Hex
Rack unknown: 0F Hex
CPU Bus Unit's duplicated unit number
0000 to 000F Hex
Special I/O Unit's duplicated unit number
8000 to 805F Hex
Duplicated Rack number (overlapping word alloca-
tions)
0000 to 0006 Hex
Error Cause
Bits 00 to 03: Error defined by Inner Board
Bits 04 to 15: Invalid
Section 3-30
S+1
Error details