Data Control Instructions
P1
R
3-18-8 SCALING 3: SCL3(487)
Purpose
Ladder Symbol
Variations
Applicable Program Areas
712
When CIO 000000 is ON, the contents of CIO 2005 is scaled using the linear
function defined by ∆ X (0FA0), ∆ Y (0400), and the offset (07D0). These values
are contained in D00100 to D00102, and the result is output to D00200.
Contents of R (D00200)
Offset
07D0 Hex
0FA0 Hex
(∆X)
Converts signed BCD data into signed binary data according to the specified
linear function. An offset can be input in defining the linear function.
SCL3(487)
S
P1
R
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program
Step program
areas
OK
OK
P1:
D00100
P1+1:
D00101
P1+2:
D00102
0400 (∆Y)
Contents of S (CIO 0200)
S: Source word
P1: First parameter word
R: Result word
Subroutines
areas
OK
Section 3-18
Offset
∆X
0 F A
0
∆Y
SCL3(487)
@SCL3(487)
Not supported.
Interrupt tasks
OK