Omron CS1G/H-CPUxxH Instructions Manual page 229

Sysmac cs series; sysmac cj series
Hide thumbs Also See for CS1G/H-CPUxxH:
Table of Contents

Advertisement

Timer and Counter Instructions
Variations
Applicable Program Areas
Operands
Operand Specifications
208
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program areas
Not allowed
OK
N: Timer Number
The timer number must be between 0000 and 4095 (decimal).
S: Set Value
The set value must be between #0000 and 9999 (BCD).
(If the set value is set to #0000, the Completion Flag will be turned ON when
TIM/TIMX(550) is executed.)
Area
CIO Area
---
Work Area
---
Holding Bit Area
---
Auxiliary Bit Area
---
Timer Area
0000 to 4095 (decimal)
Counter Area
---
DM Area
---
EM Area without bank
---
EM Area with bank
---
Indirect DM/EM
---
addresses in binary
Indirect DM/EM
---
addresses in BCD
Constants
---
Data Registers
---
Index Registers
---
Indirect addressing
,IR0 to ,IR15
using Index Registers
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
Step program areas
Subroutines
OK
N
Section 3-6
TIM/TIMX(550)
Not supported.
Not supported.
Interrupt tasks
Not allowed
S
CIO 0000 to CIO 6143
W000 to W511
H000 to H511
A000 to A959
T0000 to T4095
C0000 to C4095
D00000 to D32767
E00000 to E32767
En_00000 to En_32767
(n = 0 to C)
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to
@ En_32767
(n = 0 to C)
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_032767
(n = 0 to C)
BCD:
#0000 to 9999 (BCD)
"&" cannot be used.
Binary:
&0 to &65535 (decimal)
#0000 to #FFFF (hex)
DR0 to DR15
---

Advertisement

Table of Contents
loading

Table of Contents