Failure Diagnosis Instructions
Operands
Operand Specifications
Generating User-defined Fatal Errors
The following table shows the function of the operands.
Note The value of operand N must be different from the content of A529
(the system-generated FAL/FALS number).
Operand
N
1 to 511 (These FALS numbers are shared with FAL numbers.)
S
Specifies the first of eight words containing an ASCII message to be
displayed on the Programming Device.
Specify a constant (0000 to FFFF) if a message isn't required.
Generating Fatal Errors from the System (CS1-H, CJ1-H, CJ1M, or CS1D
Only)
The following table shows the function of the operands.
Note The value of operand N must be the same as the content of A529
(the system-generated FAL/FALS number).
Operand
N
1 to 511 (These FALS numbers are shared with FAL numbers.)
S
Error code that will be generated. (See Description below.)
S+1
Error details code that will be generated. (See Description below.)
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Counter Area
DM Area
EM Area without bank
EM Area with bank
Indirect DM/EM
addresses in binary
Indirect DM/EM
addresses in BCD
Constants
Data Registers
Index Registers
Indirect addressing
using Index Registers
Function
Function
N
---
CIO 0000 to CIO 6143
---
W000 to W511
---
H000 to H511
---
A000 to A959
---
T0000 to T4095
---
C0000 to C4095
---
D00000 to D32767
---
E00000 to E32767
---
En_00000 to En_32767
(n = 0 to C)
---
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
---
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Specified val-
#0000 to #FFFF
ues only
(binary)
---
---
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047
,IR15
DR0 to DR15, IR0 to IR15
,IR+(++)0 to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Section 3-30
S
943