Timer and Counter Instructions
Flags
Precautions
214
Name
Error Flag
Equals Flag
Negative Flag
Note In CS1 and CJ1 CPU Units, these are turned OFF.
In CS1-H, CJ1-H, CJ1M, and CS1D CPU Units, these Flags are left
unchanged.
Timer numbers are shared by the TIM, TIMX(550), TIMH(015), TIMHX(551),
TMHH(540),
TIMWX(816), TMHW(815), and TMHWX(817) instructions. If two timers share
the same timer number, but are not used simultaneously, a duplication error
will be generated when the program is checked, but the timers will operate
normally. Timers which share the same timer number will not operate properly
if they are used simultaneously.
Timers created with timer numbers 2048 to 4095 will not operate properly
when the CPU Unit cycle time exceeds 80 ms. Use timer numbers 0000 to
2047 when the cycle time is longer than 80 ms.
TIMH(015)/TIMHX(551) timers created with timer numbers 0000 to 0255 are
refreshed every 10 ms. Use these timer numbers when the PV is being refer-
enced in the user program.
The present value of timers programmed with timer numbers 0000 to 2047 will
be updated even when the timer is on standby. The present value of timers
programmed with timer numbers 2048 to 4095 will be held when the timer is
on standby.
The operation of the = Flag and N Flag depends on the model of the CPU
Unit. Refer to Flags, above, for details.
The Completion Flags for TIMH(015)/TIMHX(551) timers will be updated
when the instruction is executed. (This operation differs from that for CV-
series and CVM1 PLCs.)
Timers will be reset or paused in the following cases. (When a timer is reset,
its PV is reset to the SV and its Completion Flag is turned OFF.)
Operating mode changed from RUN or
MONITOR mode to PROGRAM mode or
1
vice versa.
Power supply interrupted and reset
Execution of CNR(545)/CNRX(547), the
RESET TIMER/COUNTER instructions
Operation in interlocked program section
(IL(002)–ILC(003))
Operation in jumped program section
(JMP(004)–JME(005))
Note
1. If the IOM Hold Bit (A50012) has been turned ON, the status of timer Com-
pletion Flags and PVs will be maintained when the operating mode is
changed.
Label
ER
ON if N is indirectly addressed through an Index Register
but the address in the Index Register is not the PV
address of a timer.
ON if in BCD mode and S does not contain BCD data.
OFF in all other cases.
=
OFF or unchanged (See note.)
N
OFF or unchanged (See note.)
TMHHX(552),
TTIM(087),
Condition
2
3
Operation
TTIMX(555),
PV
Completion Flag
0000
OFF
0000
OFF
BCD: 9999
OFF
Binary: FFFF
Reset to SV.
OFF
PV continues
Retains previous status.
decrementing.
Section 3-6
TIMW(813),