Omron CS1G/H-CPUxxH Instructions Manual page 220

Sysmac cs series; sysmac cj series
Hide thumbs Also See for CS1G/H-CPUxxH:
Table of Contents

Advertisement

Sequence Control Instructions
3-5-6
MULTIPLE JUMP and JUMP END: JMP0(515) and JME0(516)
Purpose
Ladder Symbols
Variations
Applicable Program Areas
Note For CJPN(511), the ON/OFF status of CIO 000000 would be reversed.
When the execution condition for JMP0(515) is OFF, all instructions from
JMP0(515) to the next JME0(516) in the program are processed as
NOP(000). Use JMP0(515) and JME0(516) in pairs. There is no limit on the
number of pairs that can be used in the program.
Variations
Jumps when OFF/Doesn't jump when ON
Immediate Refreshing Specification
Variations
Executed Each Cycle for ON Condition
Immediate Refreshing Specification
Block program areas
Not allowed
CIO 000000
ON
&1
Instructions
not
executed.
(Outputs re-
main un-
changed.)
&1
JMP0(515)
JME0(516)
Step program areas
Subroutines
Not allowed
OK
Section 3-5
CIO 000000
OFF
Normal
execution
JMP0(515)
Not supported
JME0(516)
Not supported
Interrupt tasks
OK
199

Advertisement

Table of Contents
loading

Table of Contents