Sequence Control Instructions
Item
Bits in OUT, OUT NOT, OUTB(534)
Status of timer instructions
(except (TTIM(087), TTIMX(555),
MTIM(543), and MTIMX(554))
Flags
Precautions
Treatment in
IL(002)/ILC(003)
OFF
Reset
Name
Error Flag
ER
Equals Flag
=
Negative Flag
N
Note In CS1 and CJ1 CPU Units, the Equals and Negative Flags are turned OFF.
In CS1-H, CJ1-H, CJ1M, and CS1D CPU Units, the Equals and Negative
Flags are left unchanged.
The cycle time is not shortened when a section of the program is interlocked
because the interlocked instructions are executed internally.
The operation of DIFU(013), DIFD(014), and differentiated instructions is not
dependent solely on the status of the execution condition when they are pro-
grammed between IL(002) and ILC(003). Changes in the execution condition
for DIFU(013), DIFD(014), or a differentiated instruction are not recorded if the
DIFU(013) or DIFD(014) is in an interlocked section and the execution condi-
tion for the IL(002) is OFF.
In general, IL(002) and ILC(003) are used in pairs, although it is possible to
use more than one IL(002) with a single ILC(003) as shown in the following
diagram. If IL(002) and ILC(003) aren't paired, an error message will appear
when the program check is performed but the program will be executed prop-
erly.
Execution
condition
a
b
OFF
ON
OFF
OFF
ON
OFF
ON
ON
All outputs retain their previous status.
Operating timers (TIM, TIMX(550),
TIMH(015), TIMHX(551), TMHH(540),
TMHHX(552) only) continue timing
because the PVs are updated even
when the timer instruction isn't being
executed.
Label
OFF
OFF or unchanged (See note.)
OFF or unchanged (See note.)
Program section
A
Interlocked
Interlocked
Interlocked
Interlocked
Not interlocked
Interlocked
Not interlocked
Not interlocked
Section 3-5
Treatment in
JMP(004)/JME(005)
Operation
B
189