High-speed Counter/Pulse Output Instructions
Applicable Program Areas
Operands
Operand Specifications
774
Block program areas
OK
P: Port Specifier
P specifies the port to which the operation applies.
P
0000 hex
Pulse output 0
0001 hex
Pulse output 1
0010 hex
High-speed counter 0
0011 hex
High-speed counter 1
0100 hex
Interrupt input 0 in counter mode
0101 hex
Interrupt input 1 in counter mode
0102 hex
Interrupt input 2 in counter mode
0103 hex
Interrupt input 3 in counter mode
1000 hex
PWM(891) output 0
1001 hex
PWM(891) output 1
C: Control Data
The function of INI(880) is determined by the control data, C.
C
0000 hex
Reads the PV.
0001 hex
Reads status.
0002 hex
Reads range comparison results.
0003 hex
Reads the high-speed counter frequency for
high-speed counter input 0.
D: First Destination Word
The PV is output to D or to D and D+1.
15
Lower word of PV
D
D+1
Upper word of PV
2-word PV
Pulse output PV, high-speed counter input PV,
high-speed counter input frequency for high-speed counter input 0
15
D
PV
1-word PV
Interrupt input PV in counter mode, status, range comparison results
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Counter Area
DM Area
EM Area without bank
EM Area with bank
Step program areas
OK
OK
Port
PRV(881) function
0
0
P
C
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Section 3-21
Subroutines
Interrupt tasks
OK
D
CIO 0000 to CIO 6143
W000 to W511
H000 to H511
A448 to A959
T0000 to T4095
C0000 to C4095
D00000 to D32767
---
---