Table Data Processing Instructions
3-17-15 STACK DATA READ: SREAD(639)
Purpose
Ladder Symbol
Variations
Applicable Program Areas
Operands
662
Reads the data from the specified data element in the stack. The offset value
indicates the location of the desired data element (how many data elements
before the current pointer position).
This instruction is supported by the CS1-H, CJ1-H, CJ1M, and CS1D CPU
Units only.
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program areas
OK
OK
TB through TB+3: Stack control words
The first four words of the stack contain the PLC memory address of the last
word in the stack and the stack pointer (the PLC memory address of the next
available word in the stack.)
15
TB
15
TB+1
15
TB+2
15
TB+3
SREAD(639)
TB: First stack address
TB
C: Offset value
C
D: Destination word
D
Step program areas
Subroutines
OK
0
PLC memory address of the last
word in the stack (rightmost 4 digits)
0
PLC memory address of the last
word in the stack (leftmost 4 digits)
0
Stack pointer (rightmost 4 digits)
(Initial value is the rightmost 4 digits
of the PLC memory address for
0
Stack pointer (leftmost 4 digits)
(Initial value is the leftmost 4 digits of
the PLC memory address for TB+4.)
Section 3-17
SREAD(639)
@SREAD(639)
Not supported.
Interrupt tasks
OK