Table Data Processing Instructions
Variations
Applicable Program Areas
Operands
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program areas
OK
C and C+1: Control words
C specifies the number of words in the range, bit 15 of C+1 indicates whether
the data will be treated as signed binary or unsigned binary, and bit 14 of C+1
indicates whether or not to output the PLC memory address of the word that
contains the maximum value to IR00.
Note C and C+1 must be in the same data area.
C
C+1
The following table shows the possible values of C.
C+1
Data type
0000
Unsigned binary
4000
Unsigned binary
8000
Signed binary
C000
Signed binary
R1: First word in range
R1 specifies the first word in the search range. The words from R1 to R1+(C–
1) are searched for the maximum value. (C is the number of words specified in
C.)
Note R1 and R1+(C–1) must be in the same data area.
Step program areas
OK
15
Number of words in range
15
14
13
00 0000
0000
0
Output selection
0: Does not output address to IR00.
1: Outputs address to IR00.
Data type
0: Unsigned binary data
1: Signed binary data
Index Register output
No
Yes
No
Yes
15
Search range
R1
to
---
R1+(C–1)
Section 3-17
MAX(182)
@MAX(182)
Not supported.
Subroutines
Interrupt tasks
OK
OK
0
0
0000
0
647