3.1.7.2 Variation 2:Starting up with the WAGO BootP Server

This procedure contains the following steps:
1. Noting the MAC-ID and establishing the fieldbus node
2. Connecting the PC and fieldbus node
3. Determining the IP address
4. Allocation of the IP address to the fieldbus node
5. Function of the fieldbus tests
6. Deactivating the BootP Protocol
Note
When starting up the 750-872/020-000 controller, there are a number of
important factors to consider, since the start-up of this controller differs
significantly in certain respects from the 750-842 ETHERNET controller.

3.1.7.2.1 Note the MAC-ID and establish the Fieldbus Node

Before establishing your fieldbus node, please note the hardware address
(MAC-ID) of your ETHERNET fieldbus controller.
This is located on the rear of the fieldbus controller and on a self-adhesive
tear-off label on the side of the fieldbus controller.
MAC-ID of the fieldbus controller:

3.1.7.2.2 Connecting PC and Fieldbus Node

Connect the assembled Telecontrol fieldbus nodeto a hub using a standard
Ethernet cable, or directly to the PC with a "crossover" cable. The
transmission rate of the controller is dependant on the baud rate of the PC
network interface card.
Attention
For a direct connection to a PC, a "crossover" cable is required instead of a
parallel cable.
Now start the BootP server on the PC and apply power to the controller (DC
24 V power pack). Once the operating voltage has been switched on, the PFC
initialization starts. The fieldbus controller determines the configuration of the
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
prompt.
cycle power on the controller until the BootP protocol has been disabled in
the PFC.
Fieldbus Controller
Fieldbus Controller 750-872/020-000
----- ----- ----- ----- ----- -----.
• 69