44 • Fieldbus Coupler/Controller
Fieldbus Coupler 750-306

3.1.2.5 Configuration Interface

The configuration interface used for the communication with
WAGO-I/O-CHECK or for firmware transfer is located behind the cover flap.
Configuration
interface
Fig. 3-5: Configuration interface
The communication cable (750-920) is connected to the 4-pole header.

3.1.2.6 Hardware Address (MAC ID)

The DIP switch is used both for parametrizing (setting the baud rate) of the
fieldbus Coupler and for setting the MAC ID.
The MAC-ID (node address) is set with the DIP switches 1 to 6 by 'sliding' the
desired DIP switch to 'ON'.
The binary significance of the individual DIP switches increases according to
the switch number. DIP switch 1 being the lowest bit with the value 2
switch 6 the highest bit with the value 2
DIP1 = ON, the MAC ID 8 with DIP4 = ON, etc.
For the DeviceNet fieldbus nodes, the node address can be set within the range
from 0 to 63.
1
2
3
4
5
6
7
8
Fig. 3-6: Example: Setting of station (node) address MAC ID 1 (DIP 1 = ON)
The configuration is only read during the power up sequence. Changing the
switch position during operation does not change the configuration of the
buscoupler. Turn off and on the power supply for the fieldbus coupler to ac-
cept the DIP switch change.
The default setting is MAC ID 1.
open
flap
ON
5
. Therefore the MAC ID 1 is set with
WAGO-I/O-SYSTEM 750
g01xx06e
0
and
g012540x
DeviceNet