148 •
Fieldbus Communication

MODBUS Functions

4.2 MODBUS Functions

4.2.1 General

MODBUS is a manufacturer-independent, open fieldbus standard for diverse
applications in manufacturing and process automation.
The MODBUS protocol is implemented for the transmission of the process
image, the fieldbus variables, different settings and information on the
controller according to the current Internet Draft.
The data transmission in the fieldside takes place via TCP and via UDP.
The MODBUS/TCP protocol is a variation of the MODBUS protocol, which
was optimized for communication via TCP/IP connections.
This protocol was designed for data exchange in the field level (i.e. for the
exchange of I/O data in the process image).
All data packets are sent via a TCP connection with the port number 502.
MODBUS/TCP segment
The general MODBUS/TCP header is as follows:
Byte:
Fig. 4-12: MODBUS/TCP Header
More information
The structure of a datagram is specific for the individual function. Refer to the
descriptions of the MODBUS Function Codes.
For the MODBUS protocol 15 connections are made available over TCP.
Thus it allows digital and analog output data to be directly read out at a
fieldbus node and special functions to be executed by way of simple
MODBUS function codes from 15 stations simultaneously.
For this purpose a set of MODBUS functions from the OPEN MODBUS /TCP
SPECIFICATION is realized.
More information
More information on the OPEN MODBUS / TCP SPECIFICATION you can
find in the Internet: www.modbus.org.
Therefore the MODBUS protocol based essentially on the following basic
data types:
Datatype
Discrete Inputs
Coils
Input Register
Holding Register
For each basic data type one or more „FunctionCodes" are defined.
0
1
2
3
Identifier
Protocol-
(entered by
identifier
receiver)
(is always 0)
Length
1 Bit
1 Bit
16 Bit
16 Bit
4
5
6
Length field
Unit
(High byte,
identifier
Low byte)
(Slave address)
Description
Digital Inputs
Digital Outputs
Analog-Input data
Analog-Output data
7
8 - n
MODBUS
Data
function code
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP