Diagnostics Via Profinet; Table 61 Led States - Ethernet Status; Table 62 Led States; Table 63 Port Status - WAGO 765-1103/100-000 Manual

16-channel digital output; profinet; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-1103/100-000
LED State
Flickering (load-dependent)
Bluetooth
The Bluetooth
tion status.
LED
BT
Port Status
LEDs 0 (port X01), 2 (port X02), 4 (port X03), ..., 14 (port X08) display the status of digital
output channel A.
LEDs 1 (port X01), 3 (port X02), 5 (port X03), ..., 15 (port X08) display the status of digital
output channel B.
LED
0, 2, 4, ...
Port status channel
A
(pin 4)
1, 3, 5, ...
Port status channel
B
(pin 2)

11.2 Diagnostics via PROFINET

General Alarms
Number
(hex)
0x0100
Product manual | Version: 2.2.0
16DO FLD PN DC 24V 2.0A
®
Status
®
LED is integrated into the Bluetooth
Color
Duo LED, blue/red
Blue
Off
Color
Duo LED, yellow/red (yellow = simultaneously red and green)
yellow
Off
red
Red
Duo LED, yellow/red (yellow = simultaneously red and green)
yellow
Off
red
Red
Alarm
Description
Undervoltage
Undervoltage in supply line 1L
The supply line has fallen below the limiting
value for the minimum voltage.
Table 61: LED States – ETHERNET Status
Description
The indicator switches on and off at a frequency of 10 Hz, indicat-
ing high ETHERNET activity: on for 50 ms and then off for 50 ms.
The indicator switches on and off at irregularity intervals to indi-
cate low ETHERNET activity.
®
antenna and indicates the connec-
State
Description
On
Bluetooth
Off
Bluetooth
State
Description
On
Status of digital output channel A: 1
Off
Status of digital output channel A: 0
On
Overload, short circuit (pin 4 and pin 3)
Flashing 1 Hz
Overload, sensor supply short circuit (pin 1
and pin 3)
On
Status of digital output channel B: 1
Off
Status of digital output channel B: 0
On
Overload, short circuit (pin 2 and pin 3)
Flashing 1 Hz
Overload, sensor supply short circuit (pin 1
and pin 3)
Diagnostics
Table 62: LED States
®
connection established
®
inactive
Table 63: Port Status
Table 64: General Alarms
Corrective Action
Check supply voltage
®
97