3.11 Terminal A2 Analog Input Signal Selection

◆ Terminal A2 Input Signal Selection

Terminal A2 can be used to input either a voltage or a current signal.
When using input A2 as a voltage input, set DIP switch S1 to "V" (left position) and set parameter H3-09 to 0 (0 to 10
Vdc) or to 1 (-10 to 10 Vdc).
To use current input at terminal A2, set the DIP switch S1 to "I" (default setting) and H3-09 = 2 or 3 (4 to 20 mA or 0 to
20 mA).
To set the DIP switch on the terminal board, use an appropriate sized tool with a tip of approximately 0.8 mm in width.
Figure 3.39
Note: If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create
the frequency reference.
Setting
V (left position)
I (right position) (default)
No.
Parameter Name
H3-09
Terminal A2 signal level selection
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual

3.11 Terminal A2 Analog Input Signal Selection

Figure 3.33 DIP Switch S1
Table 3.18 DIP Switch S1 Settings
Voltage input (-10 to +10 V)
Current input (4 to 20 mA or 0 to 20 mA): default setting
Table 3.19 Parameter H3-09 Details
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
Dip Switch S1
V
I
YEC_common
Description
Description
Setting
Default
Range
Setting
3
0 to 3
2