Main Circuit Terminals - Mitsubishi Electric FR-F800 Series Instruction Manual

Hide thumbs Also See for FR-F800 Series:

Advertisement

2.5
2.5.1
Terminal
symbol
R/L1, S/L2, T/
L3
U, V, W
R1/L11, S1/
L21
P/+, N/-
P/+, P1
PX, PR, P3
*1
Available when used in the common bus regeneration mode
Downloaded from
ManualsNet.com

Main circuit terminals

Details on the main circuit terminals
Terminal name
AC power input
Inverter output
Power supply for the control circuit
Brake unit connection
DC reactor connection for the FR-
F820-02330(55K) or lower or the
FR-F840-01160(55K) or lower
DC reactor connection for the FR-
F820-03160(75K) or higher or the
FR-F840-01800(75K) or higher
Do not use terminals PX, PR, and P3. The terminal PX is provided for the FR-F820-00490(11K) or lower and the
FR-F840-00250(11K) or lower. The terminal PR is provided for the FR-F820-01250(30K) or lower and the FR-
F840-01800(75K) or lower. The terminal P3 is provided for the FR-F820-00770(18.5K) to 01540(37K) and the FR-
F840-00470(22K) to 01800(75K).
Earth (ground)
search engine
Terminal function description
Connect these terminals to the commercial power supply.
Do not connect anything to these terminals when using the high power factor
converter (FR-HC2), multifunction regeneration converter (FR-XC)
power regeneration common converter (FR-CV).
Connect these terminals to a three-phase squirrel cage motor or a PM motor. —
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, or to use the high power factor converter (FR-
HC2), multifunction regeneration converter (FR-XC)
regeneration common converter (FR-CV), remove the jumpers across
terminals R/L1 and R1/L11 and across S/L2 and S1/L21, and supply external
power to these terminals.
The power capacity necessary when separate power is supplied from R1/
L11 and S1/L21 differs according to the inverter capacity.
FR-F820-00630(15K) or lower or FR-F840-00380(18.5K) or lower: 60 VA,
FR-F820-00770(18.5K) or higher or FR-F840-00470(22K) or higher: 80 VA
Connect the brake unit (FR-BU2, FR-BU, BU), power regeneration common
converter (FR-CV), power regeneration converter (MT-RC), high power
factor converter (FR-HC2), multifunction regeneration converter (FR-XC), or
DC power supply (under DC feeding mode).
Remove the jumper across terminals P/+ and P1, and connect a DC reactor.
When a DC reactor is not connected, the jumper across terminals P/+ and
P1 should not be removed.
Always connect a DC reactor, which is available as an option.
For earthing (grounding) the inverter chassis. Be sure to earth (ground) the
inverter.
Refer to
page
*1
, or
*1
, or power
69
80
88
59
2. INSTALLATION AND WIRING
2.5 Main circuit terminals
1
2
3
4
5
6
7
8
9
10
49