 Connection diagram
To prevent restart at failure occurrence, connect terminals So (SO) and SOC to the reset button, which are the feedback input
terminals of the safety relay module.
RESET
Emergency
stop button
 Safety stop function operation
Internal
Input
safety circuit
power
OFF
Normal
Normal
Normal
Normal
ON
Fault
Fault
Fault
Fault
*1
The terminal ON state shows that the terminal is conducted (the line is closed), and the OFF state shows that the terminal is not conducted (the
line is open).
*2
When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and SD to use the inverter. (In the initial status,
terminals S1 and PC, S2 and PC, and SIC and SD are respectively shorted with shorting wires.)
*3
If any of the faults shown in the following table occurs, terminal So (SO) and the SAFE signal turns OFF.
Fault type
Option fault
Communication option fault
Parameter storage device fault
(control circuit board)
Retry count excess
Parameter storage device fault
(main circuit board)
Internal storage device fault
Operation panel power supply
short circuit/RS-485 terminals
power supply short circuit
Downloaded from
ManualsNet.com
Safety relay module /
Safety programmable controller
*1*2
Input terminal
status
S1
S2
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
Operation panel indication
E.OPT
E.OP1
E.PE
E.RET
E.PE2
E.PE6
E.CTE
search engine
So (SO)
Logic
SOC
+24V
PC
CPU
24 VDC
S2
S1
SIC
SD
Output
Output
*8*9*10
terminal
signal
Inverter operating status
So (SO)
SAFE
OFF
OFF
Output shutoff (Safe state) Not displayed
*3
OFF
Operation enabled
ON
*4
*4
Output shutoff (Safe state) Displayed
OFF
OFF
*4
*4
Output shutoff (Safe state) Displayed
OFF
OFF
*3
*3
Output shutoff (Safe state) Not displayed
ON
ON
OFF
OFF
Output shutoff (Safe state) Displayed
OFF
OFF
Output shutoff (Safe state) Displayed
OFF
OFF
Output shutoff (Safe state) Displayed
OFF
OFF
Output shutoff (Safe state) Displayed
24 VDC power fault
Safety circuit fault
Overspeed occurrence
CPU fault
Internal circuit fault
Inverter
R/L1 S/L2 T/L3
Gate
Gate
ASIC
Driver
Driver
G
G
Operation panel indication
E.SAF
Not displayed
Fault type
Operation panel indication
E.P24
E.SAF
E.OS
E.CPU
E.5 to E.7
E.13
2. INSTALLATION AND WIRING
1
2
3
4
IGBTs
5
6
7
U V W
M
8
9
*6
*7
SA
Not displayed
10
Not displayed
Displayed
Displayed
Displayed
*5
Not displayed
Displayed
Displayed
Displayed
75
2.6 Control circuit