 Running with analog input voltage
• For the frequency setting signal, input 0 to 5 VDC (or 0 to 10 VDC) between terminals 2 and 5. The 5 V (10 V) input is the
maximum output frequency.
• The power supply 5 V (10 V) can be input by either using the internal power supply or preparing an external power supply.
The internal power supply is 5 VDC output between terminals 10 and 5, and 10 VDC output between terminals 10E and 5.
Terminal
10
10E
• To supply the 10 VDC input to terminal 2, set "0, 2, 4, 10, 12, or 14" in Pr.73. (The initial value is 0 to 5 V.)
• Set "1 (0 to 5 VDC)" or "2 (0 to 10 VDC)" in Pr.267 and turn OFF the voltage/current input selection switch to input voltage
through terminal 4. Turning ON the AU signal activates the terminal 4 input.
Forward
rotation
0 to 5 VDC
Frequency
setting
Connection diagram using
terminal 2 (0 to 5 VDC)
NOTE
• The wiring length of terminal 10, 2, and 5 should be 30 m at maximum.
 Running with analog input current
• For constant pressure or temperature control with fans, pumps, or other devices, automatic operation is available by setting
the regulator output signal 4 to 20 mADC to between terminals 4 and 5.
• To use terminal 4, the AU signal needs to be turned ON.
Forward
rotation
4 to 20mADC
Current
Frequency
input
setting
equipment
Connection diagram using
terminal 4 (4 to 20mADC)
• Set "6, 7, 16, or 17" in Pr.73 and turn ON the voltage/current input selection switch to input current through terminal 2. In
this case, the AU signal does not need to be turned ON.
Forward
rotation
4 to 20mADC
Current
Frequency
input
setting
equipment
Connection diagram using
terminal 2 (4 to 20mADC)
Downloaded from
ManualsNet.com
Inverter internal power source
voltage
5 VDC
10 VDC
Inverter
STF
Voltage/current
SD
input switch
10
Frequency
2
setting
5
2
4
Inverter
STF
AU
Voltage/current
input switch
SD
4
5
2
4
Inverter
STF
Voltage/current
SD
input switch
2
5
2
4
search engine
Frequency setting resolution
0.030/60 Hz
0.015/60 Hz
Inverter
Forward
STF
Voltage/current
rotation
SD
input switch
0 to 10 VDC
10E
2
5
2
4
Connection diagram
using terminal 2 (0 to 10 VDC)
Pr.73 (terminal 2 input voltage)
0 to 5 VDC input
0 to 10 VDC input
Forward
STF
rotation
AU
Terminal 4
input selection
SD
0 to 5 VDC
10
Frequency
4
setting
5
Connection diagram
using terminal 4 (0 to 5 VDC)
5. PARAMETERS
5.9 (T) Multi-function input terminal parameters
1
2
3
4
5
Inverter
Voltage/current
input switch
6
2
4
7
8
9
10