Mitsubishi Electric FR-F800 Series Instruction Manual page 407

Hide thumbs Also See for FR-F800 Series:

Advertisement

*4
To use the signal, assign the function to the output terminal Pr.190 to Pr.195 (Output terminal function selection) of the converter unit. Always
set the negative logic for the ALM signal.
NOTE
• To use the electronic bypass function, the wiring terminals R1/L11 and S1/L21 must be connected to a separate power source
that does not go through MC1. Be sure to connect using a separate power supply.
• Be sure to provide a mechanical interlock for MC2 and MC3.
• Operation of magnetic contactor (MC1, MC2, MC3)
Magnetic
contactor
MC1
MC2
MC3
• The input signals are as shown below.
Signal
Applied terminal
*1
MRS
MRS
CS
CS
STF
STF
(STR)
(STR)
Set "7" in any
OH
parameter from
Pr.180 to Pr.189.
RES
RES
Set "95 or 96" in any
X95/X96
parameter from
Pr.180 to Pr.189.
*1
For separated converter types, the X10 signal is assigned to the terminal MRS in the initial setting. For the MRS signal, set "24" to any of Pr.180
to Pr.189 (Input terminal function selection) to assign the function to another terminal.
*2
When the MRS signal is OFF, neither the commercial power supply operation nor the inverter operation can be performed.
*3
Terminal CS is initially set to "no function". To enable the CS signal, set "6" in Pr.186 CS terminal function selection to assign the function to
a terminal. The CS signal operates only when the MRS signal is ON.
*4
STF (STR) operates only when the MRS and CS signals are both ON.
*5
The RES signal can be used for reset input acceptance with Pr.75 Reset selection/disconnected PU detection/PU stop selection. When the
RES signal and another input signal are simultaneously input, the MC operation by the RES signal has a higher priority.
*6
MC1 turns OFF at an inverter fault.
*7
When Pr.138 = "0 (electronic bypass invalid at a fault)", MC2 is OFF. When Pr.138 = "1 (electronic bypass valid at a fault)", MC2 is ON.
406
5. PARAMETERS
5.11 (A) Application parameters
Downloaded from
ManualsNet.com
Installation location
Between power supply and
inverter input side
Between power supply and
motor
Between inverter output side
and motor
Function
Selects whether or not
operation is available.
Inverter/commercial power
supply operation
*3
switchover
Inverter operation command
(Disabled during
commercial power supply
*4
operation)
External thermal relay input
Operation status reset
Converter unit fault /
Converter unit fault (E.OHT,
E.CPU)
search engine
During commercial
During inverter
power supply
operation
Shorted
Shorted
Shorted
Open
Open
Shorted
Operation status
ON Electronic bypass operation
available
*2
OFF Electronic bypass operation not
available
ON Inverter operation
OFF Commercial power supply
operation
ON Forward rotation (reverse rotation) ○
OFF Stop
ON Motor normal
OFF Motor fault
ON Reset
*5
OFF Normal operation
X95 signal OFF, X96 signal OFF
Converter fault (E.OHT, E.CPU)
X95 signal ON, X96 signal ON
Converter normal
X95 signal OFF, X96 signal ON
Converter fault (other than E.OHT or
E.CPU)
Operation status
During inverter fault
operation
Open
(short by reset)
Open
(Selected by Pr.138. Always open
when the external thermal relay is
operating.)
Open
MC operation
*6
MC1
×
×
×
×
×
×
No change ×
×
×
×
*8
MC2
MC3
No change
×
×
No change
×
*7
×