Pr.
610
PID measured value
A625
input selection
1015
Integral stop selection at
A607
limited frequency
1346
PID lower limit operation
A457
detection time
1370
Detection time for PID
A442
limiting operation
1460
PID multistage set point 1
A683
1461
PID multistage set point 2
A684
1462
PID multistage set point 3
A685
1463
PID multistage set point 4
A686
1464
PID multistage set point 5
A687
1465
PID multistage set point 6
A688
1466
PID multistage set point 7
A689
420
5. PARAMETERS
5.11 (A) Application parameters
Downloaded from
ManualsNet.com
Name
Initial value
3
0
9999
0 s
9999
search engine
Setting range
1
Terminal 1 input
2
Terminal 2 input
3
Terminal 4 input
4
Communication input
5
PLC function input
101
Terminal 1 input
102
Terminal 2 input
103
Terminal 4 input
104
Communication input
105
PLC function input
Integral stopped at the limit, manipulation range of ±100%, integral
0
cleared during output interruption
Integral continued at the limit, manipulation range of ±100%,
1
integral cleared during output interruption
Integral stopped at the limit, manipulation range of 0 to 100%,
2
integral cleared during output interruption
Integral stopped at the limit, manipulation range of ±100%, integral
10
stopped during output interruption
Integral continued at the limit, manipulation range of ±100%,
11
integral stopped during output interruption
Integral stopped at the limit, manipulation range of 0 to 100%,
12
integral stopped during output interruption
Set the time from when the measured value input falls below the
0 to 900 s
Pr.132 setting until the FDN signal is output.
9999
As set in Pr.1370.
Set the time from when the measured value input exceeds the
0 to 900 s
Pr.131 or Pr.132 setting until the FUP or FDN signal is output.
Seven set points can be set according to the combination of the
0% to 100%
PDI1, PDI2, and PDI3 signals.
9999: Not selected
Description
Direct input of the measured value
Input of the square root of the