• When the output frequency reaches f0 and the X37 signal turns ON, the inverter begins traverse operation and accelerates
to f0 + f1. The acceleration time at this time is according to the Pr.596 setting. (If the X37 signal turns ON before the output
frequency reaches f0, traverse operation begins after the output frequency reaches f0.)
• After the inverter accelerates the motor to f0 + f1, this is compensated with f2 (f1 × Pr.594), and the motor decelerates to
f0 - f1. The deceleration time at this time is according to the Pr.597 setting.
• After the inverter decelerates the motor to f0 - f1, this is compensated with f3 (f1 × Pr.595), and the motor accelerates again
to f0 + f1.
• When the X37 signal turns OFF during traverse operation, the inverter accelerates/decelerates the motor to f0 according
to the normal acceleration/deceleration time (Pr.7, Pr.8). If the start command (STF or STR) is turned OFF during traverse
operation, the inverter decelerates the motor to a stop according to the normal deceleration time (Pr.8).
NOTE
• If the set frequency (f0) and traverse operation parameters (Pr.593 to Pr.597) are changed during traverse operation, this is
applied in operations after the output frequency reaches f0 before the change was made.
• If the output frequency exceeds Pr.1 Maximum frequency or Pr.2 Minimum frequency during traverse operation, the output
frequency is clamped at the maximum/minimum frequency when the set pattern exceeds the maximum/minimum frequency.
• When the traverse function and S-pattern acceleration/deceleration (Pr.29 ≠ "0") are selected, S-pattern acceleration/
deceleration operation occurs only in the range operated at the normal acceleration/deceleration time (Pr.7, Pr.8).
Acceleration/deceleration during traverse operation is performed linearly.
• If stall prevention activates during traverse operation, traverse operation stops and normal operation begins. When stall
prevention operation is completed, the inverter accelerates/decelerates to f0 at the normal acceleration/deceleration time
(Pr.7, Pr.8). After the output frequency reaches f0, the traverse operation begins again.
• If the value of the amplitude inversion compensation amount (Pr.594, Pr.595) is too large, an overvoltage trip or stall
prevention occurs, and pattern operation cannot be performed as set.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.3 Base
frequencypage 552
Pr.178 to Pr.189 (Input terminal function
Pr.190 to Pr.196 (Output terminal function
5.11.5 Cleaning function
This is a function to remove stains or foreign matter on the impellers or fans of pumps by setting a forward/reverse rotation
sequence.
Pr.
1469
Number of cleaning times
A420
monitor
1470
Number of cleaning times
A421
setting
1471
Cleaning trigger selection
A422
1472
Cleaning reverse rotation
A423
frequency
1473
Cleaning reverse rotation
A424
operation time
1474
Cleaning forward rotation
A425
frequency
1475
Cleaning forward rotation
A426
operation time
1476
Cleaning stop time
A427
1477
Cleaning acceleration time
A428
1478
Cleaning deceleration time
A429
1479
Cleaning time trigger
A430
Downloaded from
ManualsNet.com
selection)page 373
selection)page 330
Name
Initial value
0
0
0
30 Hz
5 s
9999
9999
5 s
9999
9999
0
search engine
Setting range
0 to 255
Displays the number of cleaning times. (Read-only)
0 to 255
Set the number of cleaning times.
0 to 15
Select the condition to start cleaning.
0 to 590 Hz
Set the reverse rotation frequency for cleaning operation.
Set the operating time after the cleaning forward rotation
0 to 3600 s
frequency is reached.
0 to 590 Hz
Set the forward rotation frequency for cleaning operation.
9999
As set in Pr.1472.
Set the operating time after the cleaning forward rotation
0 to 3600 s
frequency is reached.
9999
As set in Pr.1473.
Set the stop time when the rotation is switched from
0 to 3600 s
forward to reverse or from reverse to forward.
0 to 3600 s
Set the acceleration time for cleaning.
9999
Acceleration time for normal operation.
0 to 3600 s
Set the deceleration time for cleaning.
9999
Deceleration time for normal operation.
0
Time trigger disabled
0.1 to 6000 h
Cleaning is performed at a set time interval.
Description
5. PARAMETERS
5.11 (A) Application parameters