Mitsubishi Electric FR-F800 Series Instruction Manual page 363

Hide thumbs Also See for FR-F800 Series:

Advertisement

 Adjustment by changing the frequency without adjusting the voltage (current) (Example of
changing the gain frequency from 60 Hz to 50 Hz)
Operating procedure
1.
Selecting the parameter
Turn
Press
2.
Changing the maximum frequency
Turn
Press
3.
Selecting the mode and the monitor item
Press
4.
Start
Turn ON the start switch (STF/STR signal), and turn the frequency setting potentiometer clockwise slowly to full.
(Refer to steps 2 and 3 in
The motor is operated at 50 Hz.
NOTE
• If the frequency meter (display meter) connected between terminal FM and SD (CA and 5) does not indicate exactly 60 Hz,
set the calibration parameter C0 FM/CA terminal calibration. (Refer to
• If the voltage (current) values at the gain and bias frequencies are too close to each other, an error "
indicated.
• Changing C4 (Pr.903) or C7 (Pr.905) (gain adjustment) will not change Pr.20.
Input to terminal 1 (frequency setting auxiliary input) is added to the frequency setting signal.
• For operation outline of the parameter unit (FR-PU07), refer to the Instruction Manual of the FR-PU07.
• To set the value to 120 Hz or higher, the Pr.18 High speed maximum frequency needs to be 120 Hz or higher. (Refer to
page
• Use the calibration parameter C2 (Pr.902) or C5 (Pr.904) to set the bias frequency. (Refer to
CAUTION
• Be cautious when setting any value other than "0" as the bias frequency at 0 V (0 mA). Even if a speed command is not
given, simply turning ON the start signal will start the motor at the preset frequency.
Parameters referred to
Pr.1 Maximum frequency, Pr.18 High speed maximum
Pr.20 Acceleration/deceleration reference
Pr.73 Analog input selection, Pr.267 Terminal 4 input
Pr.79 Operation mode
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function
362
5. PARAMETERS
5.9 (T) Multi-function input terminal parameters
Downloaded from
ManualsNet.com
until "
" (Pr.125) appears for terminal 2, or "
to read the present set value. (60.00 Hz)
to change the set value to "
to confirm the selection. "
three times to select the monitor mode, and change the monitor item to the frequency.
page
131.)
287.)
frequencypage 287
frequencypage 228
selectionpage 349
selectionpage 240
search engine
". (50.00 Hz)
" and "
(
page
319.)
assignmentpage 352
" (Pr.126) for terminal 4.
)" are displayed alternately.
page
358.)
" may be