• Trace operation can also be set in the trace mode on the operation panel.
Monitor mode
Parameter setting mode
Function mode
 Selection of trace operation by input terminal (TRG signal, TRC signal)
• Trace operation can be selected by signal inputs.
• A forced trigger can be applied when the Trace trigger input (TRG) signal is ON.
• Sampling is started and stopped by the Trace sampling start/end (TRC) signal turning ON and OFF, respectively.
• To input the TRG signal, set "46" in any parameter from Pr.178 to Pr.189 (Input terminal function selection), and to
input the TRC signal, set "47" to assign the function to a terminal.
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
 Monitoring the trace status
• The trace status can be monitored on the operation panel by setting "38" in Pr.52 Operation panel main monitor
selection, Pr.774 to Pr.776 (Operation panel monitor selection), or Pr.992 Operation panel setting dial push
monitor selection.
The content depends on the digits on the operation panel.
Monitor value
*1
0 or no display
1
2
3
*1
The value(s) "0" to the left of the leftmost non-zero value is(are) not shown in the monitor display. For example, if no trace data is in internal RAM,
the USB memory is not accessed, no trigger is detected, and the trace operation is performed, "1" appears. (not "0001")
Downloaded from
ManualsNet.com
Trace method
1000s place
Indicates internal RAM state.
Indicates USB memory access state.
Fourth digit
No trace data in internal RAM
Trace data in internal RAM
search engine
No function
Sampling start
Forced trigger (Sampling stop)
1s place
Indicates trace operation.
100s place
10s place
Indicates trigger state.
Trace status
Third digit
USB memory not accessed
USB memory being
accessed
USB memory transfer error
USB buffer overrun
Sampling stop
Data transmission
Second digit
Trigger not detected
Trace stopped
Trigger detected
Trace operation
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
First digit
493