Main circuit terminals

2.5
Main circuit terminals
2.5.1
Details on the main circuit terminals of the
inverter
Terminal
Terminal name
symbol
U, V, W
Inverter output
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
Converter unit connection
Earth (ground)
2.5.2
Details on the main circuit terminals of the
converter unit (FR-CC2)
Terminal
Terminal name
symbol
R/L1,
S/L2,
AC power input
T/L3
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
Inverter connection
Earth (ground)
28
INSTALLATION AND WIRING
Terminal function description
Connect these terminals to a three-phase squirrel cage motor or a PM motor. -
Connected to the terminals P/+ and N/-. To retain the fault display and fault
output, or to use the converter unit (FR-CC2), remove the jumpers installed in
terminals R1/L11 and S1/L21, and apply external power supply to these
terminals.
The power capacity necessary when separate power is supplied from R1/L11
and S1/L21 is 80 VA.
Connect the converter unit (FR-CC2), brake unit (FR-BU2), or high power
factor converter (FR-HC2).
For earthing (grounding) the inverter chassis. This must be earthed
(grounded).
Terminal function description
Connect these terminals to the commercial power supply.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers across terminals R/L1 and
R1/L11 and across S/L2 and S1/L21, and supply external power to these
terminals.
The power capacity necessary when separate power is supplied from R1/L11
and S1/L21 is 80 VA.
Connect to terminals P/+ and N/- of the inverter.
For earthing (grounding) the converter unit chassis. This must be earthed
(grounded).
Refer
to page
43
24,
50
32
Refer
to page
-
43
24
32