 Adjustment by selecting the voltage (current) at the bias/gain frequency without applying
voltage (current) between terminals 2 and 5 (4 and 5) (Example of adjustment at the gain
frequency)
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Changing the operation mode
Press
3.
Selecting the parameter setting mode
Press
4.
Calibration parameter selection
Turn
5.
Selecting a parameter
Turn
"
6.
Analog voltage (current) display
Press
7.
Analog voltage (current) adjustment
When
Turn
8.
Setting completed
Press
alternately.
• Turn
• Press
• Press
NOTE
• Press
Downloaded from
ManualsNet.com
to choose the PU operation mode. The [PU] indicator turns ON.
to choose the parameter setting mode. (The parameter number read previously appears.)
until "
" appears. Press
until "
" (C4 (Pr.903) Terminal 2 frequency setting gain) appears for terminal 2, or
" (C7 (Pr.905) Terminal 4 frequency setting gain) for terminal 4.
to display the analog voltage (current) value (%) currently applied to terminal 2 (4).
is turned, the gain voltage (current) value (%) currently set to the parameter appears.
until the desired gain voltage (current) value (%) appears.
to confirm the selection. The analog voltage (current) % and "
to read another parameter.
to return to the "
twice to show the next parameter.
after step 6 to check the present bias/gain frequency setting. The setting cannot be checked after step 7.
search engine
to display "
" display.
".
(
)" are displayed
5. PARAMETERS
5.9 (T) Multi-function input terminal parameters
1
2
3
4
5
6
7
8
9
10