5.12.7 BACnet MS/TP protocol
Using BACnet MS/TP protocol, communication operation and parameter setting are available from the RS-485 terminals of the
inverter.
Pr.
52
Operation panel main
M100
monitor selection
774
Operation panel monitor
M101
selection 1
775
Operation panel monitor
M102
selection 2
776
Operation panel monitor
M103
selection 3
331
RS-485 communication
N030
station number
332
RS-485 communication
N031
speed
390
% setting reference
N054
frequency
549
Protocol selection
N000
726
Auto Baudrate/Max
N050
Master
727
Max Info Frames
N051
728
Device instance number
N052
(Upper 3 digits)
729
Device instance number
N053
(Lower 4 digits)
*1
When a value outside the setting range is set, the inverter operates at the initial value.
*2
When the Auto baudrate is used, the communication speed is changed to the detected communication speed.
Downloaded from
ManualsNet.com
Initial value
Name
FM
CA
0
9999
0
96
60 Hz
50 Hz
0
255
1
0
0
search engine
Setting range
0, 5 to 14, 17, 18, 20, 23 to
81: BACnet reception status
25, 34, 38, 40 to 45, 50 to
82: BACnet token pass counter (Displays the count of
57, 61, 62, 64, 67 to 69, 81
received token)
to 96, 98, 100
83: BACnet valid APDU counter (Displays the count of
valid APDU detection)
84: BACnet communication error counter (Displays the
count of communication error)
85: Terminal FM/CA output level (Same display as
1 to 3, 5 to 14, 17, 18, 20,
Analog Output 0)
23 to 25, 34, 38, 40 to 45,
86: Terminal AM output level (Same display as Analog
50 to 57, 61, 62, 64, 67 to
Output 1)
69, 81 to 96, 98, 100
The count of the setting values "82" and "83" returns to
"0" if the count exceeds "9999". The upper limit of the
count of the setting value "84" is "9999".
*1
Set the inverter station number (node).
0 to 127
Select the communication speed.
The setting value × 100 equals the communication
96, 192, 384, 576, 768,
speed.
*1*2
1152
For example, enter 96 to set the communication speed
of 9600 bps.
1 to 590 Hz
Set a reference frequency of the set frequency.
0
Mitsubishi inverter protocol (computer link)
1
MODBUS RTU protocol
2
BACnet MS/TP protocol
Auto baud rate (bit 7)
0: inactive, 1: active
0 to 255
Max Master (bit 0 to bit 6) setting range: 0 to 127
Maximum address for master node
Set the maximum number of frames that the inverter
1 to 255
can transmit while it owns the token.
Device identifier
0 to 419
When the figure obtained by combining the Pr.728 and
(0 to 418)
Pr.729 settings is not within "0 to 4194302", the setting
is out of range.
When Pr.728 = "419", the setting range of Pr.729 is "0
0 to 9999
to 4302".
(0 to 4302)
When Pr.729 = "4303" or more, the setting range of
Pr.728 is "0 to 418".
Description
5. PARAMETERS
5.12 (N) Communication operation parameters
1
2
3
4
5
6
7
8
9
10
533