Mitsubishi Electric FR-F800 Series Instruction Manual page 553

Hide thumbs Also See for FR-F800 Series:

Advertisement

*1
Initial value for the FR-F820-00046(0.75K) or lower and FR-F840-00023(0.75K) or lower.
*2
Initial value for the FR-F820-00077(1.5K) to FR-F820-00167(3.7K) and the FR-F840-00038(1.5K) to FR-F840-00083(3.7K).
*3
Initial value for the FR-F820-00250(5.5K), FR-F820-00340(7.5K), FR-F840-00126(5.5K), and FR-F840-00170(7.5K).
*4
Initial value for the FR-F820-00490(11K) to FR-F820-01540(37K), and the FR-F840-00250(11K) to FR-F840-00770(37K).
*5
Initial value for the FR-F820-01870(45K), FR-F820-02330(55K), FR-F840-00930(45K), and FR-F840-01160(55K).
*6
Initial value for the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
 Starting torque adjustment
• Assuming Pr.19 Base frequency voltage is 100%, set the output voltage at 0 Hz to Pr.0 (Pr.46) in percentage.
• Perform the adjustment of the parameter little by little (approximately 0.5%), and confirm the status of the motor each time.
The motor may overheat when the value is set too high. Do not use more than 10% as a guideline.
Pr.0
Pr.46
 Setting multiple torque boosts (RT signal, Pr.46)
• When changing the torque boost depending on the application or when using single inverter switching between multiple
motors, use the second torque boost.
• Pr.46 Second torque boost is enabled when the RT signal is ON.
NOTE
• The RT signal is a second function selection signal which also enables other second functions. (Refer to
• The RT signal is assigned to terminal RT in the initial status. Set "3" in one of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Set a larger value when the distance between the inverter and the motor is long or when there is not enough motor torque in
the low-speed range. It may cause overcurrent trip when it is set too large.
• Setting for Pr.0 and Pr.46 becomes enabled only when the V/F control is selected.
• When the initial value is set in Pr.0, the Pr.0 setting is automatically changed by changing the Pr.71 Applied motor or Pr.81
Number of motor poles setting. (Refer to
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.3 Base frequency, Pr.19 Base frequency
Pr.71 Applied
motorpage 379
Pr.178 to Pr.189 (Input terminal function
5.13.2 Base frequency voltage
V/F
V/F
V/F
Use this function to adjust the inverter outputs (voltage, frequency) to match with the motor rating.
Pr.
3
Base frequency
G001
19
Base frequency voltage 9999
G002
47
Second V/F (base
G011
frequency)
552
5. PARAMETERS
5.13 (G) Control parameters
Downloaded from
ManualsNet.com
100%
Output
voltage
Setting
range
0
Output
Base
frequency
frequency
(Hz)
voltagepage 552
selection)page 373
Initial value
Name
FM
60 Hz
9999
search engine
page
379.)
Setting
range
CA
50 Hz
0 to 590 Hz
Set the frequency at the rated motor torque. (50/60 Hz)
0 to 1000 V
Set the base voltage.
8888
8888
95% of the power supply voltage
9999
Same as the power supply voltage
0 to 590 Hz
Set the base frequency when the RL signal is ON.
9999
Second V/F disabled
page
377.)