Main Circuit Terminals - Mitsubishi Electric 800 Series Instruction Manual

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.5

Main circuit terminals

2.5.1
Details on the main circuit terminals
Terminal
Terminal name
symbol
R/L1,
AC power input
S/L2,
T/L3
U, V, W
Inverter output
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
DC terminal
P/+, P1
DC reactor connection
FR-F860-00680 or lower
DC reactor connection
FR-F860-01080 or higher
P3, PR
Do not use terminals P3 and PR. The terminal PR is equipped in the FR-F860-01080 or lower. The terminal
P3 is equipped in the FR-F860-00027 to 00170 and FR-F860-00450 to 01080.
Earth (ground)
Terminal function description
Connect these terminals to the commercial power supply.
Connect these terminals to a three-phase squirrel cage motor or a PM
motor.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers across terminals R/L1
and R1/L11 and across S/L2 and S1/L21, and supply external power to
these terminals.
The power capacity necessary when separate power is supplied from R1/
L11 and S1/L21 differs according to the inverter capacity.
FR-F860-00170 or lower
60 VA
FR-F860-00320 or higher
80 VA
Connect these terminals to the DC power supply for DC feeding.
Remove the jumper across terminals P/+ and P1, and connect a DC
reactor.
When a DC reactor is not connected, the jumper across terminals P/+ and
P1 should not be removed.
Always connect a DC reactor. (The jumper is not installed for the FR-F860-
01440 or higher.)
For earthing (grounding) the inverter chassis. This must be earthed
(grounded).
Refer to
page
60
69
49
2. INSTALLATION AND WIRING
2.5 Main circuit terminals