 Connection diagram
• Terminal R1, S1 inputs
MCCB
MC1
• 24 V external power supply input
MC1
MCCB
24VDC
Standard models and IP55 compatible models
 Operation of the self power management function
• This function controls the magnetic contactor (MC) on the input side using the output relay to reduce the standby power
during inverter stop. With the terminals R1/L11 and S1/L21 (refer to
to
page
73), the main circuit power supply and control circuit power supply are separated, and the MC for main circuit power
supply is controlled by the electronic bypass MC1 signal.
• Set Pr.248 Self power management selection = "1 or 2", Pr.30 Regenerative function selection ≠ "20, 21, 120, or 121"
(other than DC feeding mode 2), and Pr.190 to Pr.196 (Output terminal function selection) = "17 (positive logic)" to
assign the Electronic bypass MC1 (MC1) signal to an output terminal.
• After the inverter is stopped and the time set in Pr.11 DC injection brake operation time and Pr.254 Main circuit power
OFF waiting time have passed, turning OFF the MC1 signal releases the MC on the input side (main circuit power supply
OFF). Set Pr.254 to prevent frequent MC operation.
• Turning ON the start signal turns ON the MC1 signal and closes the MC on the input side (main circuit power supply ON).
After the time set in Pr.137 Start waiting time has passed, the inverter starts. Set time slightly longer (about 0.3 to 0.5
second) than the time period from the MC1-ON to the actual pick-up operation of the MC is turned ON in Pr.137.
Output frequency
Power supply mode
Main circuit power supply
Downloaded from
ManualsNet.com
Inverter
U
R/L1
M
S/L2
V
T/L3
W
R1/L11
S1/L21
MC1
MC1
SE
Standard models
Inverter
R/L1
U
M
S/L2
V
T/L3
W
R1/L11
S1/L21
MC1
MC1
+24
24VDC
SD
SE
(Hz)
DC brake
Pr.11
Pr.254
STF ON
OFF
ON
MC1
RST input
ON
search engine
Converter unit
MCCB
MC1
R/L1
S/L2
T/L3
R1/L11
S1/L21
24VDC
Converter unit
MC1
MCCB
R/L1
S/L2
T/L3
R1/L11
S1/L21
+24
24VDC
SD
page
Time
Pr.137
ON
OFF
ON
R1S1 input/
RST input
external 24 V input
OFF
ON
Inverter
P/+
P/+
U
N/-
N/-
V
W
RDA
X10
RSO
RES
Y17
X94
MC1
SE
SD
R1/L11
S1/L21
SE
Separated converter type
Inverter
P/+
P/+
N/-
N/-
RDA
X10
RSO
RES
Y17
X94
MC1
SE
SD
+24
24VDC
SE
SD
Separated converter type
69) and 24 V external power supply input (refer
5.11 (A) Application parameters
1
2
M
3
MC1
24VDC
4
5
U
M
V
6
W
MC1
7
24VDC
8
9
10
411
5. PARAMETERS