5.13.6 Adjustable 5 points V/F
V/F
V/F
V/F
By setting a desired V/F characteristic from the start up to the base frequency or base voltage with the V/F control (frequency
voltage/frequency), a dedicated V/F pattern can be generated.
The optimal V/F pattern matching the torque characteristics of the facility can be set.
Pr.
71
Applied motor
C100
100
V/F1 (first frequency)
G040
101
V/F1 (first frequency
G041
voltage)
102
V/F2 (second
G042
frequency)
103
V/F2 (second frequency
G043
voltage)
104
V/F3 (third frequency)
G044
105
V/F3 (third frequency
G045
voltage)
106
V/F4 (fourth frequency)
G046
107
V/F4 (fourth frequency
G047
voltage)
108
V/F5 (fifth frequency)
G048
109
V/F5 (fifth frequency
G049
voltage)
• By setting the V/F1 (first frequency voltage/first frequency) to V/F5 parameters in advance, a desired V/F characteristic
can be obtained.
• For an example, with the equipment with large static friction factor and small dynamic friction factor, large torque is required
only at the start up, so a V/F pattern that will raise the voltage only at the low-speed range is set.
• Setting procedure
1.
Set the rated motor voltage in Pr.19 Base frequency voltage.
(No function at the setting of "9999" or "8888".)
2.
Set Pr.71 Applied motor = "2" (adjustable 5 points V/F).
3.
Set frequency and voltage to be set in Pr.100 to Pr.109.
CAUTION
• Make sure to set the parameters correctly according to the motor used. Incorrect setting may cause the motor to overheat
and burn.
558
5. PARAMETERS
5.13 (G) Control parameters
Downloaded from
ManualsNet.com
Name
Initial value
0
9999
0 V
9999
0 V
9999
0 V
9999
0 V
9999
0 V
Voltage
Base
frequency
voltage
Pr.19
Torque
boost
Pr.0
0
search engine
Setting range
Standard motor (such as SF-JR)
2
Adjustable 5 points V/F
Others
Refer to
0 to 590 Hz, 9999
0 to 1000 V
0 to 590 Hz, 9999
0 to 1000 V
0 to 590 Hz, 9999
Set each point of the V/F pattern (frequency, voltage).
9999: Do not set V/F.
0 to 1000 V
0 to 590 Hz, 9999
0 to 1000 V
0 to 590 Hz, 9999
0 to 1000 V
V/F5
V/F4
V/F3
V/F1
V/F2
Frequency
Base
V/F Characteristic
frequency
Pr.3
Description
page
379.