Mitsubishi Electric FR-F800 Series Instruction Manual page 309

Hide thumbs Also See for FR-F800 Series:

Advertisement

Monitor item
PID input pressure
value
32-bit cumulative
energy (lower 16 bits)
32-bit cumulative
energy (upper 16 bits)
32-bit cumulative
energy (lower 16 bits)
32-bit cumulative
energy (upper 16 bits)
BACnet reception
status
BACnet token pass
counter
BACnet valid APDU
counter
BACnet
communication error
counter
BACnet terminal FM/
CA output level
BACnet terminal AM
output level
Remote output value
1
Remote output value
2
Remote output value
3
Remote output value
4
PID manipulated
amount
Second PID set point 0.1%
Second PID
measured value
Second PID deviation 0.1%
Second PID
measured value 2
Second PID
manipulated amount
Control circuit
temperature
*1
Indication with a minus sign is not possible via RS-485 or MODBUS RTU communication.
*2
To monitor the item on the LCD operation panel (FR-LU08) or the parameter unit (FR-PU07) in the monitor mode, use Pr.774 to Pr.776 or the
monitor function of the FR-LU08 or the FR-PU07 for setting.
*3
The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
*4
The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
*5
On the parameter unit (FR-PU07), the unit "kW" is displayed.
*6
The increment differs according to the inverter capacity. (FR-F820-02330(55K) or lower, FR-F840-01160(55K)or lower / FR-F820-03160(75K) or
higher, FR-F840-01800(75K) or higher)
*7
Since each readout of the output voltage and output current displayed on the operation panel (FR-DU08) is a four-digit number, a value of more
than 9999 is displayed as "----".
*8
The setting is available for the standard model.
*9
The inverter regards the output current which is less than the specified current level (5% of the rated inverter current) as 0 A. Therefore, each
readout of an output current and output power may show "0" if a too small-capacity motor is used as contrasted with the inverter capacity and the
output current falls below the specified value.
*10 Available when the plug-in option is connected.
308
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
Downloaded from
ManualsNet.com
Increment
Pr.
RS-485
and unit
setting
0.1%
69
H45
1 kWh
H4D
1 kWh
H4E
0.01/0.1
H4F
*6
kWh
0.01/0.1
H50
*6
kWh
1
81
H51
1
82
H52
1
83
H53
1
84
H54
0.1%
85
H55
0.1%
86
H56
0.1%
87
H57
0.1%
88
H58
0.1%
89
H59
0.1%
90
H5A
0.1%
91
H5B
92
H5C
0.1%
93
H5D
94
H5E
0.1%
95
H5F
0.1%
96
H60
1°C
98
H62
search engine
Negative
MODBUS
indication
RTU
*1
(-)
Displays the input pressure value of the PID input
40269
pressure control function.
40277
The upper or lower 16 bits of the 32-bit cumulative
energy is displayed on each indication.
40278
It is monitored via RS-485 communication or other
communication with a communication option installed.
40279
(To find the monitor codes for each communication
option, refer to the Instruction Manual of each
communication option.)
40280
40281
Displays the BACnet reception status.
40282
Displays the count of received token.
40283
Displays the count of valid APDU detection.
40284
Displays the count of communication error detection.
Displays the value set in the Analog Output object (ID=0:
40285
Terminal FM/CA) for BACnet communication.
Displays the value set in the Analog Output object (ID=1:
Terminal AM) for BACnet communication. (A display
40286
without signs displays negative values as absolute
values.)
40287
40288
Displays the value set in Pr.656 to Pr.659 (analog
remote output). (Refer to
40289
40290
The PID control manipulated amount is displayed. (Refer
40291
to
page
40292
The set point, measured value, or deviation is displayed
40293
during the second PID control operation. (Refer to
432.)
40294
The PID measured value is displayed while the second
PID control is enabled (Pr.753 ≠ "0"), even if PID control
40295
operating conditions are not satisfied. (Refer to
432.)
The second PID control manipulated amount is
40296
displayed. (Refer to
The temperature of the control circuit board is displayed.
(Refer to
40298
When negative number not displayed: 0 to 100°C
When negative number displayed: -20 to 100°C
Description
page
343.)
432.)
page
432.)
page
347.)
page
page