NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
• Pr.178 STF terminal function selection must be set to "60" (or Pr.179 STR terminal function selection must be set to "61")
(initial value).
• When terminal 10 is used, the maximum output frequency may fluctuate in a range of ±6 Hz due to fluctuations in the output
voltage (5 ±0.5 VDC). Use Pr. 125 or Pr. C4 to adjust the output frequency at the maximum analog input as required. (Refer
to
page
• When terminal 10E is used, the maximum output frequency may fluctuate (in a range of ±2 to 3 Hz) due to fluctuations in the
output voltage (10 ±0.4 VDC). Use Pr. 125 or Pr. C4 to adjust the output frequency at the maximum analog input as required.
(Refer to
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration
Pr.178 STF terminal function selection, Pr.179 STR terminal function
132
4. BASIC OPERATION
4.6 Basic operation procedure (External operation)