5.8.14 Detection of control circuit temperature
The temperature of the control circuit board can be monitored, and a signal can be output according to a predetermined
temperature setting.
Pr.
663
Control circuit temperature
M060
signal output level
 Control circuit temperature monitoring
• The temperature of the control circuit board can be monitored within the range of 0°C to 100°C on the operation panel, or
via terminal FM/CA, or terminal AM. Refer to
• When Pr.290 Monitor negative output selection is set to enable display of the negative numbers for monitoring on the
operation panel or via terminal AM, the range of monitoring is -20°C to 100°C.
• The monitor value is a rough approximation of the change in the surrounding air temperature of the inverter. Use this
parameter to grasp the operating environment of the inverter.
 Control circuit temperature detection (Pr.663, Y207 signal)
• The Y207 signal can be output when the control circuit temperature reaches the Pr.663 setting or higher.
• To use the Y207 signal, set "207 (positive logic) or 307 (negative logic)" in any parameter from Pr.190 to Pr.196 (Output
terminal function selection) to assign the function to the output terminal.
NOTE
• The Y207 signal is turned OFF when the control circuit temperature becomes 5°C or more lower than the Pr.663 setting.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.54 FM/CA terminal function
Pr.158 AM terminal function
Pr.190 to Pr.196 (Output terminal function
Pr.290 Monitor negative output
Downloaded from
ManualsNet.com
Name
0°C
selectionpage 314
selectionpage 314
selection)page 330
selectionpage 314
search engine
Initial value
Setting range
0°C to 100°C
page 305
for information on how to select the monitor item.
Description
Set the temperature where the Y207 signal turns
ON.
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
1
2
3
4
5
6
7
8
9
10
347

Advertisement

loading