Download Print this page

Mitsubishi Electric FR-F800 Series Instruction Manual page 221

Hide thumbs Also See for FR-F800 Series:

Advertisement

5.4.19 Inverter parts life display
The degree of deterioration of the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit, and
relay contacts of terminals A, B, and C can be diagnosed on the monitor. When a part approaches the end of its life, an alarm
can be output by self diagnosis to prevent a fault. (Note that the life diagnosis of this function should be used as a guideline
only, because with the exception of the main circuit capacitor, the life values are theoretical calculations.)
Pr.
255
Life alarm status display
E700
256
Inrush current limit circuit life
*2
display
E701
257
Control circuit capacitor life
E702
display
258
Main circuit capacitor life display 100%
*2
E703
259
Main circuit capacitor life
*2
measuring
E704
506
Display estimated main circuit
*2
capacitor residual life
E705
507
Display/reset ABC1 relay contact
E706
life
508
Display/reset ABC2 relay contact
E707
life
*1
The setting range (read-only) differs depending on the inverter model (standard model, separate converter type, or IP55 compatible model).
*2
The setting is available only for standard models and IP55 compatible models.
 Life alarm display and signal output (Y90 signal, Pr.255)
• In the life diagnosis of the main circuit capacitor, the Life alarm (Y90) signal is not output unless measurement by turning OFF
the power supply is performed.
• Whether or not the parts of the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit,
internal air circulation fans, or relay contacts of terminals A, B, and C have reached the life alarm output level can be
checked with Pr.255 Life alarm status display and the Life alarm (Y90) signal. (Internal air circulation fans are equipped
with IP55 compatible models.)
bit
15
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
220
5. PARAMETERS
5.4 (E) Environment setting parameters
Downloaded from
ManualsNet.com
Name
Initial value
0
100%
100%
0
100%
100%
100%
7
0
1
bit0 Control circuit capacitor life
bit1 Main circuit capacitor life
(Standard models and IP55 compatible models only)
bit2 Cooling fan life
bit3 Inrush current limit circuit life (Standard models and IP55 compatible models only)
bit4 Life of internal air circulation fans (IP55 compatible models only)
bit5 Estimated residual-life of main circuit capacitor (Standard models and IP55 compatible models only)
bit6 ABC1 relay contact life
bit7 ABC2 relay contact life
search engine
Setting range
Displays whether or not the parts of the control circuit
capacitor, main circuit capacitor, cooling fan, and
*1
(0 to 255)
inrush current limit circuit have reached the life alarm
output level. Read-only.
Displays the deterioration degree of the inrush current
(0% to 100%)
limit circuit. Read-only.
Displays the deterioration degree of the control circuit
(0% to 100%)
capacitor. Read-only.
Displays the deterioration degree of the main circuit
capacitor. Read-only.
(0% to 100%)
The value measured by Pr.259 is displayed.
Setting "1" and turning the power supply OFF starts the
measurement of the main circuit capacitor life.
0, 1
If the setting value of Pr.259 becomes "3" after turning
(2, 3, 8, 9)
the power supply ON again, it means that the
measurement is completed. The deterioration degree is
read to Pr.258.
When "11" is set, turning OFF the power supply starts
the measurement of the main circuit capacitor life.
11
If the setting value of Pr.259 becomes "13" after turning
(12, 13, 18, 19)
the power supply ON again, it means that the
measurement is completed. The degree of
deterioration is read to Pr.258.
Displays the estimated residual life of the main circuit
(0% to 100%)
capacitor. Read-only.
Displays the degree of deterioration of the relay
0% to 100%
contacts of terminals A1, B1, and C1.
Displays the degree of deterioration of the relay
0% to 100%
contacts of terminals A2, B2, and C2.
• Pr.255 read
Description
• Pr.255 setting read
Bit image is displayed
in decimal

Advertisement