• Example of protective function by time limit (Pr.760 = "0")
• Example of protective function measured value limit (Pr.760 = "1")
 Setting multiple PID pre-charge functions
• When the second pre-charge function is set, two sets of pre-charge functions can be switched for use. The second pre-
charge function is enabled by the turning ON RT signal.
• The second pre-charge function parameters and signals function in the same way as the following parameters and signals
of the first pre-charge function. Refer to the first pre-charge function when setting the second pre-charge functions.
Classification
Parameter
Classification
Input signal
Output signal
Downloaded from
ManualsNet.com
Measured value[PSI]
Ending level
Pr.761
Output frequency[Hz]
Pr.127
0Hz
STF
Y49
Y51
ALM
Measured value[PSI]
Pr.763
Output frequency[Hz]
Pr.127
0Hz
STF
Y49
Y53
ALM
First pre-charge function parameters
Pr.
760
Pre-charge fault selection
761
Pre-charge ending level
762
Pre-charge ending time
763
Pre-charge upper detection level
764
Pre-charge time limit
1132
Pre-charge change increment amount
First pre-charge function parameters
Signal
X77
Pre-charge end command
Y49
During pre-charge operation
Y51
Pre-charge time over
Y53
Pre-charge level over
search engine
Pr.764
E.PCH
When Pr.760 = "1",
output is shut off after the motor decelerates to a stop.
E.PCH
Name
Pr.
765
766
767
768
769
1133
Name
Signal
X78
Y50
Y52
Y54
Time
When Pr.760 = "0",
output is immediately shut off.
Time
Time
Time
Second pre-charge function parameters
Name
Second pre-charge fault selection
Second pre-charge ending level
Second pre-charge ending time
Second pre-charge upper detection level
Second pre-charge time limit
Second pre-charge change increment
amount
Second pre-charge function parameters
Name
Second pre-charge end command
During second pre-charge operation
Second pre-charge time over
Second pre-charge level over
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
449