 PU operation interlock (Pr.79 = "7")
• The operation mode can be forcibly switched to the External operation mode by turning OFF the PU operation external
interlock (X12) signal. This function will be usable in a case where the inverter does not reply to external command signals
during operation due to the operation mode accidentally unswitched from the PU operation mode to the External operation
mode.
• To input the X12 signal, set "12" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign
the function. (For details on Pr.178 to Pr.189, refer to
• Set Pr.79 = "7" (PU operation interlock).
• If the X12 signal is not assigned, the function of the MRS signal is switched to the PU operation interlock signal from MRS
(output stop).
X12 (MRS) signal
ON
OFF
*1
Depends on the Pr.77 Parameter write selection setting and other parameter write conditions. (Refer to
• Functions/operations by X12 (MRS) signal ON/OFF
Operating status
Operation
mode
During stop
PU/NET
During
running
During stop
External
During
running
*1
The mode is switched to the External operation mode regardless of the ON/OFF state of the start signal (STF/STR). Thus, the motor runs under
the External operation mode when the X12 (MRS) signal turns OFF while the STF or STR signal is ON.
*2
When a fault occurs, the inverter can be reset by pressing
NOTE
• The operation mode cannot be switched to the PU operation mode with the start signal (STF/STR) ON state even if the X12
(MRS) signal turns ON.
• If the MRS signal is ON and Pr.79 is written to a value other than "7" when the MRS signal is used as the PU interlock signal,
the MRS signal will act as a regular MRS function (output stop). Also, when Pr.79 = "7", the MRS signal becomes the PU
interlock signal.
• The logic of the signal follows the setting of Pr.17 MRS input selection also when the MRS signal is used as the PU operation
interlock signal. When Pr.17 = "2", ON and OFF in the above explanation are reversed.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Downloaded from
ManualsNet.com
Operation mode
Switching of the operation mode (External, PU, and NET) is
enabled. The signal is OFF during External operation.
Operation mode is forcefully changed to the External operation
mode.
External operation is enabled.
Switching to the PU or NET operation mode from the External
operation mode is disabled.
X12 (MRS) signal
Status
*1
ON→OFF
*1
ON→OFF
OFF→ON
ON→OFF
OFF→ON
ON→OFF
search engine
page
373.)
Function/Operation
Operation
Operating status
mode
If frequency and start commands are given
*2
from external source, the inverter runs by
External
those commands.
During stop
*2
External
Running→Output stop
Output stop→Running
on the operation panel.
5.6 (D) Operation command and frequency command
Parameter writing
Enabled.
Disabled except for Pr.79.
page
206.)
Switching to PU or
NET operation mode
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled
5. PARAMETERS
1
2
3
4
*1
5
6
7
8
9
10
247