Function
Pr.
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
289
290
291
294
295
296
297
298
299
Downloaded from
ManualsNet.com
Pr.
Name
group
Self power management
A006
selection
Earth (ground) fault detection
H101
at start
G106
Stop selection
Output phase loss protection
H200
selection
T050
Override bias
T051
Override gain
Main circuit power OFF
A007
waiting time
E700
Life alarm status display
Inrush current limit circuit life
*14
E701
display
Control circuit capacitor life
E702
display
Main circuit capacitor life
*14
E703
display
Main circuit capacitor life
*14
E704
measuring
PWM frequency automatic
E602
switchover
A730
Power failure stop selection
Subtracted frequency at
A731
deceleration start
Subtraction starting
A732
frequency
Power-failure deceleration
A733
time 1
Power-failure deceleration
A734
time 2
Power failure deceleration
A735
time switchover frequency
T001
Terminal 4 input selection
Monitor decimal digits
M022
selection
E023
Parameter for manufacturer setting. Do not set.
M431
Inverter output terminal filter 5 to 50 ms, 9999
Monitor negative output
M044
selection
D100
Pulse train I/O selection
A785
UV avoidance voltage gain
Frequency change increment
E201
amount setting
E410
Password lock level
E411
Password lock/unlock
A711
Frequency search gain
Rotation direction detection
A701
selection at restarting
search engine
Minimum
Setting range
setting
increments
0 to 2
1
0, 1
1
0 to 100 s, 1000 to
0.1 s
1100 s, 8888, 9999
0, 1
1
0% to 200%
0.1%
0% to 200%
0.1%
1 to 3600 s, 9999
1 s
(0 to 255)
1
(0% to 100%)
1%
(0% to 100%)
1%
(0% to 100%)
1%
0, 1, 11
1
0, 1
1
0 to 2, 11, 12, 21, 22
1
0 to 20 Hz
0.01 Hz
0 to 590 Hz, 9999
0.01 Hz
0 to 3600 s
0.1 s
0 to 3600 s, 9999
0.1 s
0 to 590 Hz
0.01 Hz
0 to 2
1
0, 1, 9999
1
1 ms
0 to 7
1
[FM type] 0, 1, 10, 11,
20, 21, 100
1
[CA type] 0, 1
0% to 200%
0.1%
0, 0.01, 0.1, 1, 10
0.01
0 to 6, 99, 100 to 106,
1
199, 9999
(0 to 5), 1000 to 9998,
1
9999
0 to 32767, 9999
1
0, 1, 9999
1
Initial value
Refer
Customer
to page
setting
FM
CA
0
410
0
274
9999
563
1
276
50%
353
150%
353
600 s
410
0
220
100%
220
100%
220
100%
220
0
220
1
218
0
478
3 Hz
478
60 Hz 50 Hz
478
5 s
478
9999
478
60 Hz 50 Hz
478
0
349
9999
305
9999
330
305,
0
314
258,
0
314
100%
478
0
203
9999
208
9999
208
383,
9999
474
9999
466