 Output shutoff signal (MRS signal)
Output frequency
MRS signal
STF (STR)
signal
• When the Output stop (MRS) signal is turned ON while operating the inverter, the inverter output is instantaneously shut
off.
• The response time of the MRS signal is within 2 ms.
• The MRS signal is used in the following cases.
To stop the motor using a mechanical brake (e.g.
electromagnetic brake)
To provide interlock to disable the motor operation by the
inverter
To coast the motor to a stop
 MRS signal logic inversion (Pr.17 = "2")
• When "2" is set in Pr.17, the input specification of the MRS signal is changed to normally closed (NC contact). The inverter
will shut off the output when the MRS signal is turned OFF (when the contact is opened).
 Assigning a different action for each MRS signal input via
communication and external terminal (Pr.17 = "4")
• When Pr.17 = "4", the MRS signal input from an external terminal is normally closed (NC contact), and the MRS signal
input from communication is normally open (NO contact). This function is useful to perform operation via communication
while keeping the ON state of the MRS signal input from the external terminal.
External MRS
OFF
OFF
ON
ON
NOTE
• The MRS signal is assigned to terminal MRS in the initial status. By setting "24" in any parameter from Pr.178 to Pr.189 (Input
terminal function selection), the MRS signal can be assigned to the other terminal.
• When using an external terminal to input the MRS signal, the MRS signal shuts off the output in any of the operation modes.
• The MRS signal is valid regardless of whether it is input through the external terminal or via network, but when the MRS signal
is used as the Inverter run enable (X10) signal, input the signal through the external terminal.
• When the terminal assignment is changed using Pr.178 to Pr.189 (Input terminal function selection), wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function
376
5. PARAMETERS
5.9 (T) Multi-function input terminal parameters
Downloaded from
ManualsNet.com
Motor coasts
to stop
Time
ON
ON
Application
Communication MRS
OFF
ON
OFF
ON
selection)page 373
search engine
(Initial
Setting value "0"
Setting value "2"
value)
Inverter
MRS
SD
The inverter output is shut off when the mechanical brake operates.
With the MRS signal ON, the motor cannot be driven by the inverter even if
the start signal is input to the inverter.
When the start signal is turned OFF, the inverter decelerates the motor to
a stop in the preset deceleration time, but when the MRS signal is turned
ON, the motor coasts to a stop.
0
Operation enabled
Output shutoff
Output shutoff
Output shutoff
Output shutoff
Output shutoff
Output shutoff
Operation enabled
Inverter
MRS
SD
Description
Pr.17 setting
2
Output shutoff
Output shutoff
Operation enabled
Output shutoff
4