2.5
Main circuit terminals (for 6-phase rectification)
2.5.1
Details on the main circuit terminals
Terminal symbol
Terminal name
R/L1, S/L2, T/L3
AC power input
Power supply for the control
R1/L11, S1/L21
circuit
P/+, N/-
Inverter connection
Earth (ground)
2.5.2
Terminal layout of the main circuit terminals,
wiring of power supply and the inverter
FR-CC2-H315K to FR-CC2-H630K
R1/L11 S1/L21
Charge lamp
Jumper
R/L1
T/L3
S/L2
Power supply
Connect these terminals to the commercial power supply.
Connected to the AC power supply terminals R/L1 and S/L2. To retain
the fault display and fault output, remove the jumpers across terminals
R/L1 and R1/L11 and across S/L2 and S1/L21, and apply external
power to these terminals.
When using a separate power supply connected to terminals R1/L11
and S1/L21, the required power capacity is 80 VA.
Connect them to the inverter terminals P/+ and N/-.
For earthing (grounding) the converter unit chassis. Be sure to earth
(ground) the converter unit.
P/+
N/-
To inverter
Terminal function description
2. INSTALLATION AND WIRING
2.5 Main circuit terminals (for 6-phase rectification)
1
2
Refer to
3
page
—
4
51
5
32
39
6
7
8
9
10
37