Pr.75 setting
0
1
2
3
14 (initial
value)
15
16
17
100
101
102
103
114
115
116
117
1000
1001
1002
1003
1014
1015
1016
1017
1100
1101
1102
1103
1114
1115
1116
1117
*3
The setting is available for the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
 Reset selection (P.E100)
• While P.E100 = "1", or Pr.75 = "1, 3, 15, 17, 101, 103, 115, or 117", the reset command input is enabled (using the RES
signal or through communication) only when the protective function is activated.
• While P.E100 = "2" or Pr.75 = "1000, 1002, 1014, 1016, 1100, 1102, 1114, or 1116", the reset command input is enabled
(using the RES signal or through communication) only when the start signal is OFF.
• While P.E100 = "3" or Pr.75 = "1001, 1003, 1015, 1017, 1101, 1103, 1115, or 1117", the reset command input is enabled
(using the RES signal or through communication) only when the protective function is activated with the start signal OFF.
Downloaded from
ManualsNet.com
Reset input
Always enabled.
When the protective function is activated. Operation continues.
Always enabled.
When the protective function is activated. Inverter output shutoff.
Always enabled.
When the protective function is activated. Operation continues.
Always enabled.
When the protective function is activated. Inverter output shutoff.
Always enabled.
When the protective function is activated. Operation continues.
Always enabled.
When the protective function is activated. Inverter output shutoff.
Always enabled.
When the protective function is activated. Operation continues.
Always enabled.
When the protective function is activated. Inverter output shutoff.
When the start signal is OFF.
When the protective function is activated
and the start signal is OFF.
When the start signal is OFF.
When the protective function is activated
and the start signal is OFF.
When the start signal is OFF.
When the protective function is activated
and the start signal is OFF.
When the start signal is OFF.
When the protective function is activated
and the start signal is OFF.
When the start signal is OFF.
When the protective function is activated
and the start signal is OFF.
When the start signal is OFF.
When the protective function is activated
and the start signal is OFF.
When the start signal is OFF.
When the protective function is activated
and the start signal is OFF.
When the start signal is OFF.
When the protective function is activated
and the start signal is OFF.
search engine
Operation after PU
disconnection is
PU stop function
detected
Operation continues.
Disabled
Disabled
Inverter output shutoff.
Disabled
Disabled
Operation continues.
Enabled
Enabled
Inverter output shutoff.
Enabled
Enabled
Operation continues.
Disabled
Disabled
Inverter output shutoff.
Disabled
Disabled
Operation continues.
Enabled
Enabled
Inverter output shutoff.
Enabled
Enabled
Operation continues.
Disabled
Operation continues.
Disabled
Inverter output shutoff.
Disabled
Inverter output shutoff.
Disabled
Operation continues.
Enabled
Operation continues.
Enabled
Inverter output shutoff.
Enabled
Inverter output shutoff.
Enabled
Operation continues.
Disabled
Operation continues.
Disabled
Inverter output shutoff.
Disabled
Inverter output shutoff.
Disabled
Operation continues.
Enabled
Operation continues.
Enabled
Inverter output shutoff.
Enabled
Inverter output shutoff.
Enabled
Reset limit function
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
*3
Enabled
*3
Enabled
*3
Enabled
*3
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
*3
Enabled
*3
Enabled
*3
Enabled
*3
Enabled
*3
Enabled
*3
Enabled
*3
Enabled
*3
Enabled
5. PARAMETERS
5.4 (E) Environment setting parameters
1
2
3
4
5
6
7
8
9
10
197