Mitsubishi Electric FR-F800 Series Instruction Manual page 544

Hide thumbs Also See for FR-F800 Series:

Advertisement

Pr.
C18 (920)
C19 (920)
C8 (930)
C9 (930)
C10 (931)
C11 (931)
C38 (932)
C39 (932)
C40 (933)
C41 (933)
C42 (934)
C43 (934)
C44 (935)
C45 (935)
1000 to 1999
• Fault history
Register
40501
40502
40503
40504
40505
40506
40507
40508
• Product profile
Register
44001
44002
44003
44004
44005
44006
44007
44008
44009
44010
44011
44012
44013
NOTE
• When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF, HFFFF is returned.
Downloaded from
ManualsNet.com
Register
41920
Terminal 1 gain command (torque) Read/write
42110
Terminal 1 gain (torque)
Terminal 1 gain (torque)
43920
(terminal analog value)
41930
Current output bias signal
42120
Current output bias current
41931
Current output gain signal
42121
Current output gain current
41932
Terminal 4 bias command (torque) Read/write
42122
Terminal 4 bias (torque)
Terminal 4 bias (torque)
43932
(terminal analog value)
41933
Terminal 4 gain command (torque) Read/write
42123
Terminal 4 gain (torque)
Terminal 4 gain (torque)
43933
(terminal analog value)
41934
PID display bias coefficient
42124
PID display bias analog value
PID display bias analog value
43934
(terminal analog value)
41935
PID display gain coefficient
42125
PID display gain analog value
PID display gain analog value
43935
(terminal analog value)
For details on parameter names,
45000 to 45999
refer to the parameter list
140).
Definition
Fault record 1
Fault record 2
Fault record 3
Fault record 4
Fault record 5
Fault record 6
Fault record 7
Fault record 8
Definition
Model (1st and 2nd characters)
Model (3rd and 4th characters)
Model (5th and 6th characters)
Model (7th and 8th characters)
Model (9th and 10th characters)
Model (11th and 12th characters)
Model (13th and 14th characters)
Model (15th and 16th characters)
Model (17th and 18th characters)
Model (19th and 20th characters)
Capacity (1st and 2nd characters)
Capacity (3rd and 4th characters)
Capacity (5th and 6th characters)
search engine
Name
Read/write
Read/write
Read
Read/write
Read/write
Read/write
Read/write
Read/write
Read
Read/write
Read
Read/write
Read/write
Read
Read/write
Read/write
Read
(page
Read/write
Read/write
Read/write
Read
Being 2 bytes in length, the data is stored as H00○○.
Read
Refer to the lowest 1 byte for the error code. (For details on
Read
error codes, refer to
Read
The fault history is cleared by writing to register 40501.
Read
Set any value as data.
Read
Read
Read/write
Read
Read
Read
Read
The model name can be read in ASCII code.
Read
"H20" (blank code) is set for blank area.
Example) FR-F840-1 (FM type):
Read
H46, H52, H2D, H46, H38, H34, H30, H2D, H31, H20 ... H20
Read
Read
Read
Read
Read
The inverter rated capacity can be read in ASCII code.
Data read is displayed in increments of 0.1 kW (rounded
Read
down to one decimal place).
"H20" (blank code) is set for blank area.
Read
Example) 0.75K: " 7" (H20, H20, H20, H20, H20, H37)
Remarks
Analog value (%) set in C19 (920)
Analog value (%) of voltage applied to
terminal 1
Analog value (%) set in C9 (930)
Analog value (%) set in C11 (931)
Analog value (%) set in C39 (932)
Analog value (%) of the current (voltage)
applied to terminal 4
Analog value (%) set in C41 (933)
Analog value (%) of the current (voltage)
applied to terminal 4
Analog value (%) set in C43 (934)
Analog value (%) of the current (voltage)
applied to terminal 4
Analog value (%) set in C45 (935)
Analog value (%) of the current (voltage)
applied to terminal 4
The parameter number + 44000 is the
register number.
Remarks
page
592.)
Remarks
5. PARAMETERS
5.12 (N) Communication operation parameters
1
2
3
4
5
6
7
8
9
10
543