Parameters referred to
Pr.1 Maximum
frequencypage 287
Pr.52 Operation panel main monitor
Pr.81 Number of motor
Pr.800 Control method
5.8.2
The monitor item to be displayed on the operation panel or the parameter unit can be selected.
Pr.
52
Operation panel main
M100
monitor selection
774
Operation panel monitor
M101
selection 1
775
Operation panel monitor
M102
selection 2
776
Operation panel monitor
M103
selection 3
992
Operation panel setting dial
M104
push monitor selection
170
Watt-hour meter clear
M020
563
Energization time carrying-
M021
over times
268
Monitor decimal digits
M022
selection
891
Cumulative power monitor
M023
digit shifted times
171
Operation hour meter clear 9999
M030
564
Operating time carrying-
M031
over times
290
Monitor negative output
M044
selection
1018
Monitor with sign selection 9999
M045
1106
Torque monitor filter
M050
1107
Running speed monitor
M051
filter
1108
Excitation current monitor
M052
filter
Downloaded from
ManualsNet.com
selectionpage 305
polespage 177
selectionpage 177
Monitor item selection on operation panel or via
communication
Name
Initial value
0 (output
frequency)
9999
0 (set
frequency)
9999
0
9999
9999
0
0
9999
9999
9999
search engine
Setting range
0, 5 to 14, 17, 18,
20, 23 to 25, 34, 38,
Select the item monitored on the operation panel or
40 to 45, 50 to 57,
parameter unit.
61, 62, 64, 67 to 69,
Refer to
page 306
81 to 96, 98, 100
1 to 3, 5 to 14, 17,
Each of the initial items monitored on the operation panel or
18, 20, 23 to 25, 34,
parameter unit in the monitor mode (output frequency,
38, 40 to 45, 50 to
output current, and output voltage) can be switched to a
57, 61, 62, 64, 67 to
user-designated item.
69, 81 to 96, 98,
9999: Follows the Pr.52 setting.
100, 9999
0 to 3, 5 to 14, 17,
18, 20, 23 to 25, 34,
38, 40 to 45, 50 to
Select the monitor item displayed on the operation panel at
57, 61, 62, 64, 67 to
the time when the setting dial is pressed.
69, 81 to 96, 98,
100
0
Set "0" to clear the watt-hour meter.
Set "10" to monitor the cumulative power in the range of 0 to
10
9999 kWh via communication.
Set "9999" to monitor the cumulative power in the range of 0
9999
to 65535 kWh via communication.
(0 to 65535)
The number of times that the cumulative energization time
(Read-only)
exceeded 65535 hours is displayed (read-only).
0
Value is displayed in 1 increments (an integer).
1
Value is displayed in 0.1 increments.
9999
No function
Set the number of digits to move the decimal point of the
0 to 4
cumulative energy monitored value to the left.
The readout peaks out at the upper limit of readout.
The function of moving the decimal point is not available.
9999
The readout is reset to 0 when it exceeds the upper limit.
0
Set "0" to clear the operation hour meter.
The readout is always 9999. Nothing changes when "9999"
9999
is set.
(0 to 65535)
The number of times that the operating time reaches 65535
(Read-only)
hours is displayed. Read-only.
Set the availability of negative signals output via terminal
0 to 7
AM, to the operation panel, and through communication.
Select the item group to enable the indication of negative
0, 1, 9999
signed numbers.
The filter time constant is selectable for monitoring of the
0 to 5 s
torque. A larger setting results in slower response.
9999
0.3 s filter
The filter time constant is selectable for monitoring of the
0 to 5 s
running speed. A larger setting results in slower response.
9999
0.08 s filter
The filter time constant is selectable for monitoring of the
0 to 5 s
motor excitation current. A larger setting results in slower
response.
9999
0.3 s filter
Description
for the monitor item selection.
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
1
2
3
4
5
6
7
8
9
10