Mitsubishi Electric FR-F800 Series Instruction Manual page 606

Hide thumbs Also See for FR-F800 Series:

Advertisement

Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Downloaded from
ManualsNet.com
E.GF
Output side earth (ground) fault overcurrent
The inverter output is shut off if an earth (ground) fault overcurrent flows due to an earth (ground) fault that
occurred on the inverter's output side (load side).
Check for a ground fault in the motor and connection cable.
Remedy the earth (ground) fault portion.
E.LF
Output phase loss
The inverter output is shut off if one of the three phases (U, V, W) on the inverter's output side (load side) is lost.
• Check the wiring. (Check that the motor is normally operating.)
• Check that the capacity of the motor used is not smaller than that of the inverter.
• Check if a start command is given to the inverter while the motor is coasting. (PM motor control)
• Wire the cables properly.
• Input a start command after the motor stops. Alternatively, use the automatic restart after instantaneous power
failure/flying start function
E.OHT
External thermal relay operation
The inverter output is shut off if the external thermal relay provided for motor overheat protection or the internally
mounted thermal relay in the motor, etc. switches ON (contacts open). This function is available when "7" (OH
signal) is set in any parameter from Pr.178 to Pr.189 (Input terminal function selection). This protective
function is not available in the initial status. (OH signal is not assigned.)
• Check for motor overheating.
• Check that the value "7" (OH signal) is set correctly to any of Pr.178 to Pr.189 (Input terminal function
selection).
• Reduce the load and operation duty.
• Even if the relay contacts are reset automatically, the inverter will not restart unless it is reset.
E.PTC
PTC thermistor operation
The inverter output is shut off if resistance of the PTC thermistor connected between terminal 2 and terminal 10
is equal to or higher than the Pr.561 PTC thermistor protection level setting for a continuous time equal to or
longer than the setting value in Pr.1016 PTC thermistor protection detection time. When the initial value
(Pr.561 = "9999") is set, this protective function is not available.
• Check the connection with the PTC thermistor.
• Check the Pr.561 and Pr.1016 settings.
• Check the motor for operation under overload.
Reduce the load.
E.OPT
Option fault
• Appears if the AC power supply is accidentally connected to terminal R/L1, S/L2, or T/L3 when a high power
factor converter (FR-HC2), multifunction regeneration converter (FR-XC in common bus regeneration mode),
or power regeneration common converter (FR-CV) is connected to the inverter while Pr.30 Regenerative
function selection = "2".
• Appears when the switch for manufacturer setting of the plug-in option is changed.
• Appears when a communication option is connected while Pr.296 Password lock level = "0 or 100".
• Check that the AC power supply is not connected to terminal R/L1, S/L2, or T/L3 when the FR-HC2, FR-XC (in
common bus regeneration mode), or FR-CV is connected to the inverter while Pr.30 = "2".
• Check for the password lock with a setting of Pr.296 = "0, 100".
• Check the Pr.30 setting and wiring with the FR-HC2, FR-XC, or FR-CV.
• The inverter may be damaged if the AC power supply is connected to terminal R/L1, S/L2, or T/L3 when a high
power factor converter is connected. Contact your sales representative.
• Set the switch on the plug-in option, which is for manufacturer setting, back to the initial setting. (Refer to the
Instruction Manual of each option.)
• To apply the password lock when installing a communication option, set Pr.296 ≠ "0, 100". (Refer to
search engine
FR-LU08 indication Ground Fault
FR-LU08 indication Output phase loss
(page
472). (PM motor control)
FR-LU08 indication Ext TH relay oper
FR-LU08 indication PTC thermistor oper
FR-LU08 indication Option Fault
page
208.)
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
1
2
3
4
5
6
7
8
9
10
605