(b) Adjustment by selecting the voltage (current) at the bias/gain level without applying voltage (current) between terminals 1
and 5 (4 and 5)
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Changing the operation mode
Press
Calibration is also possible in the External operation mode.
3.
Selecting the parameter setting mode
Press
4.
Calibration parameter selection
Turn
5.
Selecting a parameter
Turn
(Pr.933) Terminal 4 gain (torque)) for terminal 4.
6.
Analog voltage (current) display
Press
7.
Analog voltage (current) adjustment
When
Turn
8.
Setting completed
Press
alternately.
Turn
Press
Press
NOTE
• Press
checked after step 7.
Downloaded from
ManualsNet.com
to choose the PU operation mode. [PU] indicator turns ON.
to choose the parameter setting mode. (The parameter number read previously appears.)
until "
" appears. Press
until "
" (C19 (Pr.920) Terminal 1 gain (torque)) appears for terminal 1, or "
to display the analog voltage (current) % currently applied to the terminal 1 (4).
is turned, the gain voltage (current) value (%) currently set to the parameter appears.
until the desired gain voltage (current) value (%) appears.
to confirm the selection. The analog voltage (current) % and "
to read another parameter.
to return to the "
twice to show the next parameter.
after step 6 to check the present bias/gain setting of the stall prevention operation level. The setting cannot be
search engine
to display "
".
" display.
5.9 (T) Multi-function input terminal parameters
" (C41
(
)" are displayed
5. PARAMETERS