Download Print this page

Mitsubishi Electric FR-F800 Series Instruction Manual page 428

Hide thumbs Also See for FR-F800 Series:

Advertisement

 Input/output signals
• Assigning the PID control valid (X14) signal to the input terminal by Pr.178 to Pr.189 (Input terminal function selection)
enables PID control to be performed only when the X14 signal is turned ON. When the X14 signal is OFF, regular inverter
running is performed without PID action . (When the X14 signal is not assigned, PID control is enabled only by setting
Pr.128 ≠ "0".)
• Input signal
Signal
X14
PID control valid
X80
Second PID control valid
PDI1
PID multistage set point setting 1 38
PDI2
PID multistage set point setting 2 39
PDI3
PID multistage set point setting 3 40
PID forward/reverse action
X64
switchover
Second PID forward/reverse
X79
action switchover
X72
PID P control switchover
X73
Second PID P control switchover 73
• Output signal
Signal
FUP
PID upper limit
Second PID upper
FUP2
limit
FDN
Lower limit output
Second PID lower
FDN2
limit
PID forward/reverse
RL
rotation output
Second PID forward/
RL2
reverse rotation
output
During PID control
PID
activated
During second PID
PID2
control activated
Y48
PID deviation limit
Second PID deviation
Y205
limit
PID output
SLEEP
interruption
During second PID
SLEEP2
output shutoff
NOTE
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
confirming the function of each terminal.
Downloaded from
ManualsNet.com
Pr.178 to
Function
setting
14
80
64
79
72
Pr.190 to Pr.196
setting
Function
Positive
Negative
logic
logic
15
115
201
301
14
114
200
300
16
116
202
302
47
147
203
303
48
148
205
305
70
170
204
304
search engine
Pr.189
When this signal is assigned to the input terminal, PID control is enabled
when this signal is ON.
The set point set in Pr.1460 to Pr.1466 can be selected by combining the
ON/OFF status of the signals.
PID control is switched between forward and reverse action without
changing parameters by turning ON this signal.
Integral and differential values can be reset by turning ON this signal.
Output when the measured value signal exceeds Pr.131 PID upper limit
(Pr.1143 Second PID upper limit).
Output when the measured value signal falls below Pr.132 PID lower limit
(Pr.1144 Second PID lower limit).
"Hi" is output when the output display of the parameter unit is forward rotation
(FWD) and "Low" is output when the display is reverse rotation (REV) and stop
(STOP).
Turns ON during PID control.
When the PID calculation result is reflected to the output frequency (Pr.128<
"2000"), the PID signal turns OFF at turn OFF of the start signal.
When the PID calculation result is not reflected to the output frequency (Pr.128
≥ "2000"), the PID signal turns ON during PID calculation regardless of the start
signal status.
Output when the absolute deviation value exceeds the limit value set in Pr.553
PID deviation limit (Pr.1145 Second PID deviation limit).
Set Pr.575 Output interruption detection time (Pr.1147 Second output
interruption detection time) ≠ "9999". This signal turns ON when the PID
output suspension function is activated.
Description
Description
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
427

Advertisement

loading