5.7.2
A cooling fan is built into the inverter and its operation can be controlled.
Pr.
Cooling fan
244
operation selection
Cooling fan
H100
operation selection
Cooling fan
operation selection
H106
during the test
operation
 Cooling fan always ON (Pr.244 (P.H100) = "0")
• When Pr.244 = "0", the cooling fan operates at power ON. If the fan stops at this time, the inverter finds that the fan
operation is faulty and "
output (FAN) signal and the Alarm (LF) signal are output.
• For the terminal used for the FAN signal output, set "25 (positive logic)" or "125 (negative logic)" in any parameter from
Pr.190 to Pr.196 (Output terminal function selection) and for LF signal, set "98 (positive logic)" or "198 (negative logic)".
 Cooling fan operation control (Pr.244 (P.H100) = "1" (initial value), "101 to
105")
• The cooling fan operation is controlled when Pr.244 = "1". When the inverter is running, the cooling fan operates constantly.
When the inverter is stopped, the cooling fan operates depending on the temperature of the inverter heat sink. If the fan
stops although it meets the conditions for running, fan operation is regarded as faulty, [FN] is displayed on the operation
panel, and the fan signal and LF signals are output.
• To prevent the cooling fan from turning ON and OFF repeatedly during frequent starts/stops (inching), the cooling fan stop
waiting time can be set. The waiting time when Pr.244 = "101 to 105" is Pr.244 - 100 (or 1 second, if the Pr.244 = "101").
Downloaded from
ManualsNet.com
Cooling fan operation selection
Name
Initial value
1
1
0
" (FN), the indication of the Fan alarm, is displayed on the operation panel. The Fan fault
search engine
Setting range
Cooling fan ON/OFF control disabled. (The cooling fan is always ON at
0
power ON.)
A cooling fan operates at power ON.
Cooling fan ON/OFF control enabled.
The fan is always ON while the inverter is running. During a stop, the
1
inverter status is monitored and the fan switches ON/OFF according to
the temperature.
Cooling fan ON/OFF control enabled.
101 to 105
Set the cooling fan stop delay time within 1 to 5 s.
Cooling fan ON/OFF control disabled. (The
1000
cooling fan is always ON at power ON.)
A cooling fan operates at power ON.
Cooling fan ON/OFF control enabled.
The fan is always ON while the inverter is
1001
running. During a stop, the inverter status
is monitored and the fan switches ON/OFF
according to the temperature.
Cooling fan ON/OFF control enabled.
1101 to 1105
Set the cooling fan stop delay time within 1
to 5 seconds.
Cooling fan ON/OFF control disabled. (The cooling fan is always ON at
0
power ON.)
A cooling fan operates at power ON.
Cooling fan ON/OFF control enabled.
The fan is always ON while the inverter is running. During a stop, the
1
inverter status is monitored and the fan switches ON/OFF according to
the temperature.
Cooling fan ON/OFF control enabled.
101 to 105
Set the cooling fan stop delay time within 1 to 5 s.
The cooling fan operates according to the H100 setting during PM
0
motor test operation.
The cooling fan can be set to always OFF during PM motor test
1
operation.
Description
The cooling fan can be set
to always OFF during PM
motor test operation.
5. PARAMETERS
5.7 (H) Protective function parameter
1
2
3
4
5
6
7
8
9
10
273