 Safety stop signal
Terminal
Terminal name
symbol
Safety stop input
S1
(Channel 1)
Safety stop input
S2
(Channel 2)
Safety monitor output
So (SO)
(open collector output)
 Common terminal
Terminal
Common
symbol
SD
PC
SD
5
SE
SIC
SOC
*1
Sink logic is initially set for the FM-type inverter.
*2
Source logic is initially set for the CA-type inverter.
Downloaded from
ManualsNet.com
Common
Use terminals S1 and S2 to receive the safety stop signal
input from the safety relay module. Terminals S1 and S2 can
be used at a time (dual channel).
The Inverter judges the condition of the internal safety circuit
from the status (shorted/opened) between terminals S1 and
SIC
SIC, or between S2 and SIC. When the status is opened, the
inverter output is shut off.
In the initial status, terminal S1 and S2 are shorted with
terminal PC by shorting wires. Terminal SIC is shorted with
terminal SD. Remove the shorting wires and connect the
safety relay module when using the safety stop function.
The output status varies depending on the input status of the
safety stop signals.
The output is in HIGH state during occurrence of the internal
safety circuit failure. The output is in LOW state otherwise.
(The open collector transistor is ON (conductive) in LOW
SOC
state. The transistor is OFF (not conductive) in HIGH state.)
Refer to the Safety Stop Function Instruction Manual if the
output becomes in HIGH state even though both terminals
S1 and S2 are open. (Contact your sales representative for
this manual.)
Terminal name
Contact input
Common terminal for the contact input terminal (sink logic),
*1
terminal FM.
common (sink)
Connect this terminal to the power supply common terminal of
External transistor
a transistor output (open collector output) device, such as a
*2
programmable controller, in the source logic to avoid
common (source)
malfunction by undesirable current.
Common terminal for the 24 VDC power supply (terminal PC,
24 VDC power supply
terminal +24).
common
Isolated from terminals 5 and SE.
Connect this terminal to the power supply common terminal of
External transistor
a transistor output (open collector output) device, such as a
*1
programmable controller, in the sink logic to avoid malfunction
common (sink)
by undesirable current.
Contact input
Common terminal for contact input terminal (source logic).
*2
common (source)
24 VDC power supply Can be used as a 24 VDC 0.1 A power supply.
Common terminal for the frequency setting signal (via terminal
Frequency setting
2, 1, or 4) and for the analog output terminals AM and CA. Do
common
not earth (ground).
Open collector output
Common terminal for terminals RUN, SU, OL, IPF, FU
common
Safety stop input
Common terminal for terminals S1 and S2.
terminal common
Safety monitor output
Common terminal for terminal So (SO).
terminal common
search engine
Terminal function description
Terminal function description
Refer
Rated specification
to
page
Input resistance: 4.7
kΩ, input current: 4 to 6
mADC (with 24 VDC
input)
74
Permissible load: 24
VDC (27 VDC at
maximum), 0.1 A (The
voltage drop is 3.4 V at
maximum while the
signal is ON.)
Refer
Rated specification
to
page
Power supply voltage
range: 19.2 to 28.8
65
VDC, permissible
load current: 100 mA
349
74
74