YASKAWA CPU 013C Manual page 106

For vipa system slio
Table of Contents

Advertisement

Deployment I/O periphery
Counting > SFB 47 - COUNT - Counter controlling
Parameters
Name
Data type
LADDR
WORD
CHANNEL
INT
SW_GATE
BOOL
CTRL_DO
BOOL
SET_DO
BOOL
JOB_REQ
BOOL
JOB_ID
WORD
JOB_VAL
DINT
STS_GATE
BOOL
STS_STRT
BOOL
STS_LTCH
BOOL
STS_DO
BOOL
STS_C_DN
BOOL
STS_C_UP
BOOL
COUNTVAL
DINT
LATCHVAL
DINT
JOB_DONE
BOOL
JOB_ERR
BOOL
JOB_STAT
WORD
106
Address
Default value
(Instance
DB)
0.0
300h
2.0
0
4.0
FALSE
4.1
FALSE
4.2
FALSE
4.3
FALSE
6.0
0
8.0
0
12.0
FALSE
12.1
FALSE
12.2
FALSE
12.3
FALSE
12.4
FALSE
12.5
FALSE
14.0
0
18.0
0
22.0
TRUE
22.1
FALSE
24.0
0
Comment
This parameter is not evaluated. Always the internal
I/O periphery is addressed.
Channel number
Enables the Software gate
Enables the output
False: Standard Digital Output
Parameter is not evaluated
Initiates the job (edge 0-1)
Job ID
Value for write jobs
Status of the internal gate
Status of the hardware gate
Status of the latch input
Status of the output
Status of the down-count
Always indicates the last direction of count. After
the first SFB call STS_C_DN is set FALSE.
Status of the up-count
Always indicates the last direction of count. After
the first SFB call STS_C_UP is set TRUE.
Actual count value
Actual latch value
New job can be started
Job error
Job error ID
HB300 | CPU | 013-CCF0R00 | en | 16-40